Permit Number: T02CM03972
Parcel: 124041020

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T02CM03972
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/23/2002 JIM EGAN FIRE REVIEW Approved
08/23/2002 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
08/23/2002 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied SEE COMMENTS ON BACK OF APPLICATION.
08/23/2002 HOLLY PEARCE WATER REVIEW Approved
10/14/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Approved PLEASE RETURN THE PLANS I HAVE ALREADY REVIEWED ALONG WITH YOUR NEXT SUBMISSION. IT WILL ASSIST IN MY SECOND REVIEW. Thank-you

1) The exit light in the storage room must be connected to the line side (cannot be switched) of circuit P-17. See 99NEC 700-12(e)
2) Provide an IECC lighting budget analysis. The W/ft2 for this use is 2.8.
3) Provide a complete one line service diagram and drive loads back to the building service. Provide enough information to prove adequacy of the building service.
10/25/2002 GERRY KOZIOL WWM REVIEW Approved
10/25/2002 PETER MCLAUGHLIN ZONING REVIEW Approved
11/21/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Approved
11/21/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/25/2002 MONICA VALDEZ OUT TO CUSTOMER Completed