Permit Number: T02CM03799
Parcel: 12510070A

Review Status: Completed

Review Details: REVISION

Permit Number - T02CM03799
Review Name: REVISION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/24/2003 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied GENERAL:

q There are no general comments to be addressed.

ARCHITECTURAL:

q There are no architectural comments to be addressed.

STRUCTURAL:

q How does the new sheet (Sheet S8.2) relate to the rest of the structural plans? The current approved plans do not reference any of the new details included on this new sheet. Further, the details indicate that there is a shear wall being put into the basement. What has changed to require this new shear wall? The foundation/farming plans should reference these details and there should be calculations which justify the design of this new shear wall(s), indicating that the wall will meet the load conditions that will be applied.

-End of Review-

Final Status

Task End Date Reviewer's Name Type of Review Description
04/24/2003 ELAINE ROSE OUT TO CUSTOMER Completed