Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION
Permit Number - T02CM03799
Review Name: REVISION
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/24/2003 | STANTEC | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Denied | GENERAL: q There are no general comments to be addressed. ARCHITECTURAL: q There are no architectural comments to be addressed. STRUCTURAL: q How does the new sheet (Sheet S8.2) relate to the rest of the structural plans? The current approved plans do not reference any of the new details included on this new sheet. Further, the details indicate that there is a shear wall being put into the basement. What has changed to require this new shear wall? The foundation/farming plans should reference these details and there should be calculations which justify the design of this new shear wall(s), indicating that the wall will meet the load conditions that will be applied. -End of Review- |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/24/2003 | ELAINE ROSE | OUT TO CUSTOMER | Completed |