Permit Number: T02CM03793
Parcel: 11108313B

Address:
2502 N DODGE BL

Review Status: Completed

Review Details: 3RD PARTY COMMERCIAL TI

Permit Number - T02CM03793
Review Name: 3RD PARTY COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/10/2002 DAN CASTRO ZONING REVIEW Approved
09/10/2002 WATER WATER REVIEW Approved
09/10/2002 JIM EGAN FIRE REVIEW Denied 1. OCCUPANCY APPEARS TO BE I-2(OR I-1/I-2). I-2 NOT PERMITTED IN VB OCCUPANCY.
2. INDICATE COMPLIANCE WITH 2000 IBC SEC.407.
3. PROVIDE FIRE SPRINKLER SYSTEM DESIGN CRITERIA ON PLAN. INDICATE COMPLIANCE WITH NFPA 13-1999 FOR ALL AREAS.
1. SEE SITE COMMENTS.
09/10/2002 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
09/10/2002 DAN CASTRO NPPO REVIEW Passed
10/07/2002 WILDAN 3RD PARTY REVIEW-COMMERCIAL REVIEW Approved
10/09/2002 CAGUILA1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/08/2002 CINDY AGUILAR OUT TO CUSTOMER Completed