Review Status: Completed
Review Details: 3RD PARTY COMMERCIAL TI
Permit Number - T02CM03793
Review Name: 3RD PARTY COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/10/2002 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 09/10/2002 | WATER | WATER | REVIEW | Approved | |
| 09/10/2002 | JIM EGAN | FIRE | REVIEW | Denied | 1. OCCUPANCY APPEARS TO BE I-2(OR I-1/I-2). I-2 NOT PERMITTED IN VB OCCUPANCY. 2. INDICATE COMPLIANCE WITH 2000 IBC SEC.407. 3. PROVIDE FIRE SPRINKLER SYSTEM DESIGN CRITERIA ON PLAN. INDICATE COMPLIANCE WITH NFPA 13-1999 FOR ALL AREAS. 1. SEE SITE COMMENTS. |
| 09/10/2002 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
| 09/10/2002 | DAN CASTRO | NPPO | REVIEW | Passed | |
| 10/07/2002 | WILDAN | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Approved | |
| 10/09/2002 | CAGUILA1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/08/2002 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |