Permit Number: T02CM03793
Parcel: 11108313B

Address:
2502 N DODGE BL

Review Status: Completed

Review Details: SITE

Permit Number - T02CM03793
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/16/2002 DAVID RIVERA ZONING REVIEW Denied FROM: David Rivera FOR: Patricia Gehlen
Senior Planner Principal Planner

PROJECT: T02CM03793
Residential Care Services Physical and Behavioral Health Service
2502 N Dodge Boulevard

TRANSMITTAL: August 16, 2002

COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Although the proposed use does constitute a change of use the parking lot is to be re-striped and therefore must meet code requirements such as parking spaces dimensions, PAAL widths, Handi-cap Parking spaces etc.

Based on the number (183) of provided vehicle parking spaces as noted in the calculations block, six (6) accessible (handi-cap) parking spaces must be provided. Five spaces have been labeled as accessible; one additional space is required.

The previous plan does not indicate that the sidewalks meet accessible slope requirements. Please label the slopes of the existing or proposed ramps from the accessible parking spaces to the onsite pedestrian circulation. All ramps must meet the minimum slope requirements of 1:12

2. The building square footage of the building is noted as 76,000. All residential care service facilities greater than 5000 square feet gross floor area must be provided with loading zones. Per LUC section 3.4.5.4 table 4, facilities with 75,000-sq. ft. to 150,000-sq. ft. must be provided with three (3) 12 feet by 35 feet loading zones. List in the calculation block the number of required and provided loading zones. The loading zones must be shown, labeled, and dimensioned on the plan. The maneuverability in and out of the loading zones must be demonstrated.


If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan
08/16/2002 DAVID RIVERA HANDICAP-SITE REVIEW Denied See zoning comments regarding handi-cap requirements.
09/03/2002 BLANCA ESPINO ENGINEERING REVIEW Denied Site Plan
1. Indicate property description below location map. D.S. 2-02.2.1.2

2. Indicate existing sight visibility triangles. D.S. 2-02.2.1.10

3. Dimension the loading space(s) and demonstrate maneuvering area(s). D.S. 2-02.2.1.14

4. Indicate drainage patterns with flow arrows. D.S. 2-02.2.1.16

5. Show dimensioned driveways. Standard two-way driveway is 24' in width. D.S. 2-02.2.1.21
09/03/2002 BLANCA ESPINO SANITATION REVIEW Approved
09/03/2002 BLANCA ESPINO FLOODPLAIN REVIEW Denied SEE ENGINEERING FOLDER.
09/04/2002 JIM EGAN FIRE REVIEW Denied 1. SHOW LOCATION OF EXISTING FIRE HYDRANTS ON PLAN.
2. INDICATE WHAT HAPPENS TO "REMOVE EXISTING GATE AND FENCE" PROVIDING ACCESS TO WINSTEL BLVD.
3. INDICATE NEW/EXISTING CONSTRUCTION ON PLAN.
09/17/2002 JOE LINVILLE NPPO REVIEW Approved
09/17/2002 JOE LINVILLE LANDSCAPE REVIEW Denied Revise the landscape plan to avoid significant conflicts with sight visibility. LUC 3.7.2.8

Final Status

Task End Date Reviewer's Name Type of Review Description
09/17/2002 DELMA ROBEY OUT TO CUSTOMER Completed