Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T02CM03667
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/06/2002 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/06/2002 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | Plumbing 1.Inclued the mop sink in the isometric drawing. Provide a clean out Per Sec 707.4UPC 1994 Az. Code. 2. Provide a waste line isometric drawing of the 3-comp sink, flow control and how it attaches to the grease trap. Provide a vent and clean out down stream of the G.T. 3. Provide clean outs on the hand sinks Per Sec707.41994 Az. Code. 4. On the condensate line, install the vent down stream of the trap. 5.Provide a air gap for the T&P and overflow drain at the mop sink. 6. Backflow devices shall be listed and testable. |
| 09/06/2002 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/06/2002 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |