Permit Number: T02CM03667
Parcel: 12308082A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T02CM03667
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/06/2002 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
09/06/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing 1.Inclued the mop sink in the isometric drawing. Provide a clean out Per Sec 707.4UPC 1994 Az. Code. 2. Provide a waste line isometric drawing of the 3-comp sink, flow control and how it attaches to the grease trap. Provide a vent and clean out down stream of the G.T. 3. Provide clean outs on the hand sinks Per Sec707.41994 Az. Code. 4. On the condensate line, install the vent down stream of the trap. 5.Provide a air gap for the T&P and overflow drain at the mop sink. 6. Backflow devices shall be listed and testable.
09/06/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/06/2002 MONICA VALDEZ OUT TO CUSTOMER Completed