Permit Number: T02CM03618
Parcel: 20914001C

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T02CM03618
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/01/2002 PETER MCLAUGHLIN ZONING REVIEW Passed
08/02/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Passed Mechanical 1. Provide an exhaust fan for the bathrooms.
08/02/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Approved Plumbing 1. Provide a civil site plan with FFE, septic tank location,water lines and sewer lines, size and slope of sewer lines. 2. Plan view indicates a 3" waste line from the last fixtures, isometric indicates a 4". Code requires a 4" waste line after the third W.C. 3. Show venting on the plan and the size of same. NOTE: Isometric drawing does not comply with the code for venting. 4. Provide a water demand calculation based on Appendix 'A' UPC 1994 Az. Code on the plan.
08/29/2002 JIM EGAN FIRE REVIEW Approved
08/29/2002 DROBEY1 WWM REVIEW Needs Review
08/29/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied 1) Provide fault current analysis
2) The conduits serving the sub panels must have seal offs on both ends of the conduit.
3) Provide the component short circuit current rating of the service.
08/29/2002 DROBEY1 WATER REVIEW Approved
08/29/2002 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Needs Review
08/29/2002 JIM TATE FLOODPLAIN REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/29/2002 MONICA VALDEZ OUT TO CUSTOMER Completed