Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T02CM03618
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/01/2002 | PETER MCLAUGHLIN | ZONING | REVIEW | Passed | |
08/02/2002 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Passed | Mechanical 1. Provide an exhaust fan for the bathrooms. |
08/02/2002 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Approved | Plumbing 1. Provide a civil site plan with FFE, septic tank location,water lines and sewer lines, size and slope of sewer lines. 2. Plan view indicates a 3" waste line from the last fixtures, isometric indicates a 4". Code requires a 4" waste line after the third W.C. 3. Show venting on the plan and the size of same. NOTE: Isometric drawing does not comply with the code for venting. 4. Provide a water demand calculation based on Appendix 'A' UPC 1994 Az. Code on the plan. |
08/29/2002 | JIM EGAN | FIRE | REVIEW | Approved | |
08/29/2002 | DROBEY1 | WWM | REVIEW | Needs Review | |
08/29/2002 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1) Provide fault current analysis 2) The conduits serving the sub panels must have seal offs on both ends of the conduit. 3) Provide the component short circuit current rating of the service. |
08/29/2002 | DROBEY1 | WATER | REVIEW | Approved | |
08/29/2002 | PIMA COUNTY | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
08/29/2002 | JIM TATE | FLOODPLAIN | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/29/2002 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |