Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T02CM03587
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/30/2002 | DAN CASTRO | ZONING | REVIEW | Denied | Building plans may not be approved until site plan is approved by all sections. |
| 11/26/2002 | JIM EGAN | FIRE | REVIEW | Denied | 1. SHOW LOCATION OF EXISTING FIRE HYDRANTS ON PLAN. 2. PROVIDE COMPLETE FIRE SPRINKLER SYSTEM DESIGN CRITERIA ON PLAN. a. Standard to be used. b. Hazard Classification c. Minimum design density and area of application. d. Water supply information. Static psi-Residual psi-Flow gpm. 3. fire service underground piping depicted on plan is incorrect. |
| 11/27/2002 | BLANCA ESPINO | FLOODPLAIN | REVIEW | Denied | See site plan review for comments. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/27/2002 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |