Permit Number: T02CM03587
Parcel: 103090180

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T02CM03587
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/30/2002 DAN CASTRO ZONING REVIEW Denied Building plans may not be approved until site plan is approved by all sections.
11/26/2002 JIM EGAN FIRE REVIEW Denied 1. SHOW LOCATION OF EXISTING FIRE HYDRANTS ON PLAN.
2. PROVIDE COMPLETE FIRE SPRINKLER SYSTEM DESIGN CRITERIA ON PLAN.
a. Standard to be used.
b. Hazard Classification
c. Minimum design density and area of application.
d. Water supply information. Static psi-Residual psi-Flow gpm.
3. fire service underground piping depicted on plan is incorrect.
11/27/2002 BLANCA ESPINO FLOODPLAIN REVIEW Denied See site plan review for comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/27/2002 MONICA VALDEZ OUT TO CUSTOMER Completed