Permit Number: T02CM03541
Parcel: 129040180

Address:
221 N NORRIS AV

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM

Permit Number - T02CM03541
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/21/2003 PETER MCLAUGHLIN ZONING REVIEW Approved
01/21/2003 PETER MCLAUGHLIN NPPO REVIEW Passed
01/21/2003 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
02/07/2003 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM03541

2/10/03 221 N.NORRIS AVE.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.


SITE PLAN:

1. PROVIDE A ONE HOUR FIRE WALL WHERE LESS THAN 3 FEET FROM THE PROPERTY LINE ( SEE R302 ).

FLOOR PLANS:

1. HOW WILL THIS ADDITION EFFECT EGRESS OF THE EXISTING BEDROOM ADJACENT THE ADDITION.

2. PROVIDE HANDRAILS AT STEPS WITH TWO OR MORE RISERS.


3. THE WINDOW ON THE STAIRWAY LANDING IS IN THE ONE HOUR FIREWALL. IS IT FIRE RATED?

4. HOW IS THE CRAWL SPACE UNDER THE DINING AREA VENTILATED AND ACCESSED?

5. DETAIL AND SPECIFY STAIR WIDTH (MINIMUM 36"), RISE AND RUN (MINIMUM 10" TREAD DEPTH AND 7 ¾"
MAXIMUM RISER HEIGHT PER R314), LANDING WIDTH (PER R312), AND HANDRAIL HEIGHTS (PER R315).

STRUCTURAL PLANS:

1. JUSTIFY THE CANTILEVER AND THE CONNECTIONS OF THE BALCONY RAFTERS AND THE FLOOR JOISTS.

ELEVATIONS:

1. PROVIDE FOR THE ONE HOUR WALL.








PLUMBING PLANS:

1. HORIZONTAL DRAINS FOR SINKS ARE TO BE 2 INCHES MINIMUM. SEE U.P.C. TABLE 7-5 .

2. THE MINIMUM SIZE DRAIN FOR A SHOWER IS 2 INCH.

3. WET VENTING BETWEEN FLOORS IS PROHIBITED.

4. WATER LINE: PROVIDE TOTAL FIXTURE DEMAND & MAXIMUM DEVELOPED LENGTH OF THE EXISTING DWELLING.

ELECTRICAL PLANS:

1. NOTE ON PLANS: ELECTRICAL WORK SHALL COMPLY WITH CHAPTERS 33 - 42, 2000 IRC.

2. AT LEAST ONE WALL SWITCH CONTROLLED LIGHT OR OUTLET MUST BE PROVIDED IN OUTDOOR ENTRANCES OR EXITS AND ALL HABITABLE
ROOMS PER E3801.

3. PROVIDE AN EXTERIOR OUTLET AT GRADE LEVEL LOCATED AT THE BACK OF THE
DWELLING, PER E3801.7. THIS OUTLET SHALL BE GFI PROTECTED PER E3802.3.

4. BATHROOM OUTLETS SHALL BE ON A SEPARATE 20 AMP CIRCUIT WITH NO OTHER OUTLETS, PER E3603.4.

5. ALL RECEPTACLE OUTLETS IN BATHROOMS SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTING PROTECTION. NOTE ON THE DRAWINGS AT EACH OUTLET REQUIRING SUCH PROTECTION,
PER E3802.

6. NOTE THAT LIGHT FIXTURES IN CLOTHES CLOSETS SHALL BE INSTALLED IN ACCORDANCE WITH E3903.11.

7. PLEASE NOTE R317.1.1 REQUIRES THE DWELLING TO BE PROVIDED WITH SMOKE DETECTORS.

8. A LIGHTING FIXTURE IS REQUIRED OUT SIDE THE DOOR EXITING THE LIVING ROOM. SEE E3803.3 .

MODEL ENERGY CODE:

1. PROVIDE ENERGY CALCULATIONS PER THE 1998 IECC, OR COMPLY WITH IRC CHAPTER 11.

2. CALL OUT ON THE PLANS THE "R" VALUES OF INSULATION, AS WELL AS THE "U" VALUES OF THE WINDOWS
AND DOORS IN CONFORMANCE WITH THE ENERGY CALCULATIONS PROVIDED.



IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110
02/12/2003 CAGUILA1 WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/12/2003 DELMA ROBEY OUT TO CUSTOMER Completed