Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T02CM03493
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/25/2002 | JIM EGAN | FIRE | REVIEW | Approved | |
07/25/2002 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Approved | |
07/25/2002 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | E1 1) 99NEC 230-2 allows one service per building. See COT amendments for possible exceptions. You obtain a variety of documents on line at www. cityoftucson.org/dsd 2) All services on the building must have their grounding electrodes tied together. 99NEC 250-58 3) Provide a fault current analysis based upon TEP actual fault current at the point of attachment. Provide a fully listed and labeled series rated system per 99NEC 110-3, 110-9, 110-10, 240-86 or provide full fault current analysis. 4) Unless overhead service exists on the site a special waiver will have to be submitted for review. E2 1) Provide a fixture cut with the catalog numbers for the C fixture. See COT lighting ordinance. |
07/25/2002 | ANY | FLOODPLAIN | REVIEW | Approved | |
07/25/2002 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
07/25/2002 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
07/25/2002 | FRANK KALINSKI | WATER | REVIEW | Approved | |
08/09/2002 | LLESNY1 | WWM | REVIEW | Needs Review | |
08/09/2002 | LLESNY1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/09/2002 | LISA LESNY | OUT TO CUSTOMER | Completed |