Permit Number: T02CM03493
Parcel: 106060180

Address:
1354 W PRINCE RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T02CM03493
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/25/2002 JIM EGAN FIRE REVIEW Approved
07/25/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Approved
07/25/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied E1
1) 99NEC 230-2 allows one service per building. See COT amendments for possible exceptions. You obtain a variety of documents on line at www. cityoftucson.org/dsd
2) All services on the building must have their grounding electrodes tied together. 99NEC 250-58
3) Provide a fault current analysis based upon TEP actual fault current at the point of attachment. Provide a fully listed and labeled series rated system per 99NEC 110-3, 110-9, 110-10, 240-86 or provide full fault current analysis.
4) Unless overhead service exists on the site a special waiver will have to be submitted for review.
E2
1) Provide a fixture cut with the catalog numbers for the C fixture. See COT lighting ordinance.
07/25/2002 ANY FLOODPLAIN REVIEW Approved
07/25/2002 PETER MCLAUGHLIN ZONING REVIEW Approved
07/25/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Approved
07/25/2002 FRANK KALINSKI WATER REVIEW Approved
08/09/2002 LLESNY1 WWM REVIEW Needs Review
08/09/2002 LLESNY1 BUILDING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/09/2002 LISA LESNY OUT TO CUSTOMER Completed