Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/ZONING/FLOOD
Permit Number - T02CM03484
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/14/2002 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 11/14/2002 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
| 11/14/2002 | PETER MCLAUGHLIN | NPPO | REVIEW | Passed | |
| 11/22/2002 | DAVE WITT | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN CHECK COMMENTS - PROJECT #T02CM03484 11/22/02 2361 E. CAMERON VISTA PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN. SCOPE OF REVIEW: THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL. GENERAL REQUIREMENTS: 1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS. 2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. FOUNDATION PLANS: 1. DIMENSION FOOTING WIDTH, THICKNESS AND DEPTH INTO UNDISTURBED SOIL PER TABLE R403.1. STRUCTURAL PLANS: 1. PLEASE JUSTIFY THE 2x8@ 12" O.C. RAFTERS ON THE CARPORT. 2. SHOULD THE RAFTERS BE PERPENDICULAR TO THE RIDGE BETWEEN THE HOBBYROOM AND THE EXISTING HOUSE WITH A VALLEY FROM THE CORNER OF THE TWO WALLS TO THE RIDGE? 3. PROVIDE SUPPORT FOR THE LINE OF TRUSSES OVER THE CARPORT. 4. PROVIDE CONNECTIONS BETWEEN THE HIP FRAMING MEMBERS. 5. DETAIL GABLE END BRACING CONNECTIONS IN ACCORD WITH R802.10.3. 6. SPECIFY AND DETAIL ALL OVER FRAMING. IF SOLID SHEATHING IS USED ON THE LOWER TRUSSES, PROVIDE MINIMUM OPENINGS OF 22" BY 30" FOR ACCESS AND VENTILATION INTO OVER FRAMED AREAS (>30 S.F.). IF SOLID SHEATHING IS NOT USED ON LOWER TRUSSES, PROVIDE DETAILS FOR BRACING OF TOP CHORD OF LOWER TRUSSES. ELEVATIONS: 1. SHOW CALCULATION OF ATTIC VENTILATION AREA IN COMPLIANCE WITH R806.2. NOTE LOCATION OF ALL VENTS NEEDED TO COMPLY. SECTIONS - DETAILS - MISC. NOTES: 1. DTL. B/1 , THE GARAGE OVERHANG IS NOT PERMITTED 2' FROM THE PROPERTY LINE. PLEASE EXTEND THE FIRE RATEING TO THE ROOF DECK. 2. DTL. B/1 , NOTE 13--- DOES 5/8 O.S.B. HAVE A 1 HR. FIRE RATEING? PLEASE CORRECT OR DOCUMENT. 3. DTL. B/1 , NOTE #3, IS THE BOND BEAM REINFORCED? 4. DTL. B/1 , NOTE #10 APPEARS TO CONFLICT WITH NOTE #1. 5. DTL. 1 /4 , IS THE "2- 2X TOP PLATE" A TYPO. 6. DTL. 4 /4 , UTILIZING THE RIDGE AS A BEAM DELETES THE NEED FOR COLLARS, BUT THE 2X10 IS UNDER SIZED FOR THE BEAM AND ALSO REQUIRES SUPPORT AT EACH END. THE RIDGE BOARD IS TO COVER THE FULL WIDTH OF THE CUT END. 7. SHT. 4, "DESIGN CRITERIA", THE FLOOR DEAD LOAD APPEARS INCORRECT FOR CONCRETE. ALSO, THE FLOOR LIVE LOAD SHOULD BE 40 P.S.F. FOR THIS OCCUPANCY. 8. DTL. 3 /4 , PLEASE SHOW A MASONRY/WOOD CONNECTION. 9. STRUCTURAL NOTES, 4. LUMBER NOTE #1, SHOULD REFER TO THE 2000 IRC 10. PLBG. NOTE #5,D,2, LEAD CONTENT OF 60/40 SOLDER CONFLICTS WITH UPC 316.1.3 . ELECTRICAL PLANS: 1. A RECEPTACLE IS REQUIRED WITHIN 6' OF THE HOBBYROOM/KITCHEN DOOR. 2. READILY ACCESSIBLE RECEPTACLES IN GARAGE ARE REQUIRED TO BE GFCI PROTECTED. 3. R317.1.1 REQUIRES THE EXISTING SLEEPING AREAS TO BE PROTECTED WITH SMOKE DETECTORS. 4. RISER DIAGRAM, WHAT ARE THE 3 METERS FOR? THE BOND NOTE APPEARS TO BE FOR APARTMENTS. IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: DAVE WITT @ 791-5550 EXT. 1110 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/25/2002 | TAMI ACHONG | OUT TO CUSTOMER | Completed |