Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Permit Number - T02CM03458
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/03/2002 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 09/03/2002 | PETER MCLAUGHLIN | NPPO | REVIEW | Passed | |
| 09/03/2002 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
| 09/17/2002 | DAVE WITT | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN CHECK COMMENTS - PROJECT #T02CM03458 9/17/02 1048 E. HEDRICK DR. PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN. SCOPE OF REVIEW: THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL. GENERAL REQUIREMENTS: 1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE. 2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS. 3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. 4. LIST THE SQUARE FOOTAGES FOR ALL THE FOLLOWING AREAS SEPARATELY ON THE DRAWINGS: - LIVABLE AREA - GARAGE - PORCH/PATIO COVERS - DECKS SITE PLAN: 1. PROVIDE A SITE PLAN INDICATING THE LOCATION OF ALL STRUCTURES ON YOUR PROPERTY. 2. PROVIDE DIMENSIONS FROM THE STRUCTURE TO PROPERTY LINES. FOUNDATION PLANS: 1. NOTE ON THE DRAWINGS THE ALLOWABLE SOIL BEARING PRESSURE USED IN THE DESIGN OF THE FOOTINGS, OR STATE THAT THE ASSUMED VALUE OF 1500 PSF IS BEING USED, PER TABLE R401.4.1, A SOILS REPORT IS NOT REQUIRED. IT IS UP TO THE DESIGNER/HOMEBUILDER TO BE AWARE OF THE SOIL AND CONDITIONS OF THE SITE. IF SOIL TESTING HAS BEEN DONE, A COPY OF THE SOILS REPORT SHALL BE SUBMITTED WITH THE CONSTRUCTION PLANS, AND THE FOUNDATION DESIGN SHALL REFLECT THE SOILS REPORTS RECOMMENDATIONS. 2. PROVIDE A FOUNDATION PLAN. 3. NOTE AND DETAIL MINIMUM REINFORCING, OR PROVIDE CODE JUSTIFICATION OF ALTERNATE: - MONOLITHIC - ONE (1) #5 OR TWO (2) #4 REBARS IN THE MIDDLE OF THE FOOTING. - STEMWALL - ONE (1) #4 REBAR IN THE BOTTOM OF THE FOOTING AND ONE (1) #4 REBAR IN THE TOP OF THE STEM ON BRACED WALLS PER R602.10.6 - STEMWALL (WITH UNBALANCED FILL) - PER TABLE R404.1.1 (1-4) 4. FOOTING WIDTHS FOR ONE-STORY, PER TABLE R403.1: - 16" MINIMUM; WOOD FRAME - 19" MINIMUM; HOLLOW CONCRETE/MASONRY - 22" MINIMUM; SOLID FULLY GROUTED/MASONRY 5. LOCATE AND DETAIL ALL FOOTINGS FOR THE FOLLOWING: - FIREPLACE - INTERIOR BEARING WALLS - POSTS 6. ALL SLABS AND PADS, INCLUDING LANDINGS AT ALL DOORS, SHALL BE SHOWN AND THEIR THICKNESS SPECIFIED. INDICATE THE SLOPE FOR EXTERIOR SLABS, PER R312. 7. LOCATE AND SPECIFY ALL ANCHOR BOLT SPACING AND POST ANCHORS ON THE FOUNDATION PLAN. 8. ALL FOUNDATION HOLD-DOWNS AND ANCHOR BOLT SPACING FOR SHEAR WALLS SHALL BE SPECIFIED AND LOCATED. FLOOR PLANS: 1. LABEL ALL ROOMS AND SPACES. SHOW ALL DOORS. SHOW ENTIRE FLOOR PLAN. 2. PROVIDE ALL WINDOW SIZES AND TYPES, AND DESIGNATE THE OPERABLE PORTION OF WINDOWS, AS WELL AS THE LOCATIONS OF TEMPERED GLASS PER R308.4. 3. NOTE THAT BATHTUB AND SHOWER ENCLOSURES SHALL BE FINISHED PER p2710 WITH CERAMIC TILE, OR A LISTED ENCLOSURE, TO A HEIGHT OF 72" ABOVE THE DRAIN PER R702.4 AND R307.2 4. FIREPLACES: - INDICATE FIREPLACE LOCATION, HEARTH SIZE AND MATERIALS, PER R1003.10 OR R1004.2 - FOR FACTORY BUILT OR ZERO CLEARANCE FIREPLACES, PROVIDE CUT SHEETS, MAKE, MODEL NUMBER AND THE APPROVAL NUMBER OF THE APPROVED TESTING AGENCY (IE: ICBO #), PER R1002 ALL SHALL COMPLY WITH UL127. - FOR MASONRY FIREPLACES, SHOW CROSS-SECTION, PER R100. 5. IDENTIFY CEILING HEIGHTS IN ALL AREAS ON FLOOR PLAN. IF SLOPED CEILING, NOTE AVERAGE HEIGHT. STRUCTURAL PLANS: 1. SPECIFY LUMBER GRADE AND SPECIES. 2. COMPLETELY DETAIL ALL CONNECTIONS AND CROSS-REFERENCE TO THE FOUNDATION AND FRAMING PLANS: - RAFTER TO TOP PLATE - BEAM TO POST - POST TO SLAB - SILL TO SLAB, ANCHOR BOLT SIZES AND SPACING, POST TO SILL PLATE 3. NOTE AND DETAIL FRAMING ANCHORS BY NAME. ELEVATIONS: 1. NOTE AND SIZE ALL ROOF DRAINS OR SCUPPERS ON FLAT-ROOFED AREAS PER R903.4. 2. SHOW CALCULATION OF ATTIC VENTILATION AREA IN COMPLIANCE WITH R806.2. NOTE LOCATION OF ALL VENTS NEEDED TO COMPLY. 3. NOTE AND DIMENSION THAT THE FIREPLACE CHIMNEY MUST TERMINATE A MINIMUM OF 2' ABOVE ANY POINT OF ROOF WITHIN 10' MEASURED HORIZONTALLY AND NOT LESS THAN 3' ABOVE THE POINT WHERE THE CHIMNEY PASSES THROUGH THE ROOF, PER R1001.6 SECTIONS - DETAILS - MISC. NOTES: 1. PROVIDE A BUILDING CROSS-SECTION. MORE THAN ONE MAY BE REQUIRED TO CLEARLY ILLUSTRATE HOW THE STRUCTURE IS BUILT. CROSS REFERENCE THE SECTION TO THE FLOOR PLAN. 2. NOTE AND SPECIFY THE SIZE, SPACING AND LENGTH OF ANCHOR BOLTS FOR SILL PLATES, TOP PLATES AND LEDGERS. 3. NOTE AND SPECIFY ALL LEDGERS AND CONNECTIONS TO WOOD, FRAME OR MASONRY. 4. DETAIL THE FIREPLACE. PROVIDE DIMENSIONED AND NOTED CROSS SECTION. PLUMBING PLANS: 1. NOTE AND SPECIFY ALL PIPING MATERIALS. 2. PROVIDE AN ISOMETRIC DRAWING OF WASTE LINES. SHOW SIZES OF WASTE LINES, VENTS AND REQUIRED CLEANOUTS. 3. WATER LINE: PROVIDE TOTAL FIXTURE DEMAND & MAXIMUM DEVELOPED LENGTH 4. NOTE ON PLAN COMPLIANCE WITH WATER CONSERVATION; WATER CLOSETS 1.6 GALLONS PER FLUSH, SINKS AND SHOWERHEADS 3 GALLONS PER MINUTE. 5. NOTE ON PLANS THAT SHOWER AND TUB / SHOWER COMBINATIONS THAT HAVE INDIVIDUAL CONTROL VALVES SHALL BE OF THE PRESSURE BALANCE OR THERMOSTATIC MIXING VALVE TYPE. MECHANICAL PLANS: 1. NOTE ON PLANS: MECHANICAL SHALL COMPLY WITH CHAPTERS 12 - 24 2000 IRC. 2. THE DWELLING MUST BE PROVIDED WITH HEATING CAPABLE OF MAINTAINING A ROOM TEMPERATURE OF 68 DEGREES AT A POINT 3' ABOVE THE FLOOR PER R303.6. SPECIFY THE HEATING UNIT. 3. SHOW EXHAUST FAN LOCATION FOR THE BATHROOM. ELECTRICAL PLANS: 1. NOTE ON PLANS: ELECTRICAL WORK SHALL COMPLY WITH CHAPTERS 33 - 42, 2000 IRC. 2. DESIGNATE THE LOCATION AND CIRCUIT OF ALL REQUIRED LIGHT FIXTURES, RECEPTACLE OUTLETS, POWER OUTLETS AND SWITCHES. PROVIDE A PANEL SCHEDULE NOTING CIRCUIT NUMBER AND SIZE ALONG WITH A GENERAL DESCRIPTION. 3. PROVIDE AN EXTERIOR OUTLET AT GRADE LEVEL LOCATED AT BOTH THE FRONT AND BACK OF THE DWELLING, PER E3801.7. THESE OUTLETS SHALL BE GFI PROTECTED PER E3802.3. 4. RECEPTACLE OUTLETS SHALL BE PROVIDED AT EACH KITCHEN COUNTER SPACE WIDER THAN 12", AND SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24" FROM A RECEPTACLE OUTLET, PER E3801.4.1 SUPERIMPOSE THE RECEPTACLES AND LIGHTS ON A FLOOR PLAN FOR THE ADDITIONS. 5. BATHROOM OUTLETS SHALL BE ON A SEPARATE 20 AMP CIRCUIT WITH NO OTHER OUTLETS, PER E33603.4. 6. ALL RECEPTACLE OUTLETS IN BATHROOMS AND KITCHENS SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTING PROTECTION. NOTE ON THE DRAWINGS AT EACH OUTLET REQUIRING SUCH PROTECTION, PER E3802. 7. NOTE THAT TWO OR MORE 2OAMP SMALL APPLIANCE CIRCUITS SHALL BE PROVIDED TO SERVE ALL RECEPTACLE OUTLETS IN THE KITCHEN, BREAKFAST ROOM AND DINING ROOM. SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS, PER E3603.2 AND E3801.3-4.5. 8. SUBMIT PANEL SCHEDULE SHOWING CIRCUIT AMPACITY, WIRE SIZES, PANEL SIZE AND CIRCUIT NUMBERS. 9. SUBMIT ELECTRICAL RISER DIAGRAM. 10. SHOW LOCATIONS OF SMOKE DETECTORS PER R317. NOTE THAT ALL SMOKE DETECTORS MUST BE INTERCONNECTED WITH A POWER SOURCE FROM THE BUILDING WIRING, AND SHALL BE EQUIPPED WITH BATTERY BACKUP. MODEL ENERGY CODE: 1. PROVIDE ENERGY CALCULATIONS PER THE 1998 IECC, OR COMPLY WITH IRC CHAPTER 11. 2. CALL OUT ON THE PLANS THE "R" VALUES OF INSULATION, AS WELL AS THE "U" VALUES OF THE WINDOWS AND DOORS IN CONFORMANCE WITH THE ENERGY CALCULATIONS PROVIDED. IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: DAVE WITT @ 791-5550 EXT. 1110 ADDITIONAL PLAN CHECK COMMENTS THERE ARE SO MANY APPARENT DEFICIENCIES IN THE PLANS |
| 09/21/2002 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/26/2002 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |