| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/08/2002 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied | City of Tucson, Development Services BUILDING AND STRUCTURAL COMMENTS 1) Provide the correct formula for the beam deflection shown on sheet 1 of calc`s and run the computations. Check the deflection for total loads. 2) Specify the species, Commercial Grade, size classification and Grading Rules Agency per the 2000 IBC. 3) Seismic and Wind analysis shall be performed as per the 2000 IBC. |