Permit Number: T02CM03447
Parcel: 107083140

Address:
800 W GRANT RD

Review Status: Stopped

Review Details: RESUBMITTAL

Permit Number - T02CM03447
Review Name: RESUBMITTAL
Review Status: Stopped
Review Date Reviewer's Name Type of Review Description Status Comments
10/08/2002 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied City of Tucson, Development Services
BUILDING AND STRUCTURAL COMMENTS



1) Provide the correct formula for the beam deflection shown on sheet 1 of calc`s and
run the computations. Check the deflection for total loads.

2) Specify the species, Commercial Grade, size classification and Grading Rules Agency per the 2000 IBC.

3) Seismic and Wind analysis shall be performed as per the 2000 IBC.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/30/2002 ELAINE ROSE OUT TO CUSTOMER Stop