Review Date Reviewer's Name Type of Review Description Status Comments
07/23/2002 DAN CASTRO ZONING REVIEW Passed
07/23/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied 1) It appears the Main Bonding Jumper must be a minimum of 350 kcmil. 99NEC 250-102(c).
2) It appears the taps to the panel should be 11/2" minimum conduit size. This assumes EMT conduit longer than 24" filled not to exceed 40%. 99NEC Tables Chapter 9.
3) Provide a scaled site plan showing the relative proximity of the service to the modular units. This is needed to assure the shortest distance to a unit does not exceed 22,000 amps of fault.
07/23/2002 JAMES TATE FLOODPLAIN REVIEW Approved