Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T02CM03441
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/23/2002 | DAN CASTRO | ZONING | REVIEW | Passed | |
| 07/23/2002 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1) It appears the Main Bonding Jumper must be a minimum of 350 kcmil. 99NEC 250-102(c). 2) It appears the taps to the panel should be 11/2" minimum conduit size. This assumes EMT conduit longer than 24" filled not to exceed 40%. 99NEC Tables Chapter 9. 3) Provide a scaled site plan showing the relative proximity of the service to the modular units. This is needed to assure the shortest distance to a unit does not exceed 22,000 amps of fault. |
| 07/23/2002 | JAMES TATE | FLOODPLAIN | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/25/2002 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |