Permit Number: T02CM03383
Parcel: 11305004A

Address:
2330 E PRINCE RD

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM

Permit Number - T02CM03383
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/17/2002 BLANCA ESPINO FLOODPLAIN REVIEW Approved
07/29/2002 DAN CASTRO ZONING REVIEW Approved
07/30/2002 JOE LINVILLE NPPO REVIEW Approved 5 protected plants preserved in plce and 4 mitigation PV required
08/08/2002 REYES ARVAYO BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM03383

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

FLOOR PLANS:

1.. LOCATE AND IDENTIFY SHEAR WALL TYPES AND LOCATIONS - CLARIFY LOCATION OF SSTB16 -ALSO ON FOUNDATION PLAN

FOUNDATION PLANS:

1. ALL FOUNDATION HOLD-DOWNS AND ANCHOR BOLT SPACING FOR SHEAR WALLS SHALL BE SPECIFIED AND
LOCATED. SSTB16

STRUCTURAL PLANS:

1. PROVIDE COMPLETE ROOF AND FLOOR FRAMING PLANS. SHOW SIZE, SPACING AND SPAN OF ALL FRAMING
MEMBERS, TRUSSES, JOISTS, RAFTERS, BEAMS, GLULAMS, LINTELS, HEADERS, LEDGERS AND BLOCKING.


2. SPECIFY LATERAL SUPPORT OF TRUSSES.

3. DETAIL ALL CONNECTIONS AND CROSS-REFERENCE TO THE FOUNDATION AND FRAMING
PLANS:

- POST TO SLAB
- CONTINUOUS LOAD PATH FOR SHEAR TRANSFER
- TRUSSES ROOF DIAPHRAGM- BLKING -NAILING ECT. ECT.
- SUPPORTS UNDER GIRDER TRUSS


ELEVATIONS:

1. INDICATE ALL MATERIALS USED; STUCCO, CONCRETE BLOCK, GLASS BLOCK, ROOFING SYSTEMS, SIDING,
VENEERS, ETC.

2. NOTE AND SPECIFY ALL ROOF SLOPES APPROPRIATE TO MATERIAL (SEE R905).

3. NOTE AND SIZE ALL ROOF DRAINS OR SCUPPERS ON FLAT-ROOFED AREAS PER R903.4.

4. SHOW CALCULATION OF ATTIC VENTILATION AREA IN COMPLIANCE WITH R806.2. NOTE LOCATION OF ALL
VENTS NEEDED TO COMPLY.

5. FOAM INSULATION: CLARIFY YOUR COMPLIANCE WITH R318 ON THE MAIN WALLS AND THOSE WALLS TO
THE ATTIC PER R318.2.3.

PLUMBING PLANS:

1. NOTE AND SPECIFY ALL PIPING MATERIALS.



2. GAS: PROVIDE THE LENGTH OF LINE TO EACH APPLIANCE, BTU DEMAND OF EACH APPLIANCE, SIZE OF
EACH BRANCH, TOTAL DEMAND & TOTAL DEVELOPED LENGTH FROM METER TO MOST REMOTE
APPLIANCE ON THE SYSTEM PER UPC 1217.2 SHOW SIZE OF GAS LINE TO FIRST APPL.

3. NOTE ON PLAN COMPLIANCE WITH WATER CONSERVATION; WATER CLOSETS 1.6 GALLONS PER FLUSH, SINKS
AND SHOWERHEADS 3 GALLONS PER MINUTE.

4. SHOW LOCATION OF PRESSURE AND TEMPERATURE RELIEF VALVE AT WATER HEATER.

5. NOTE ON PLANS THAT SHOWER AND TUB / SHOWER COMBINATIONS THAT HAVE INDIVIDUAL CONTROL
VALVES SHALL BE OF THE PRESSURE BALANCE OR THERMOSTATIC MIXING VALVE TYPE.

6. PROVIDE DETAIL ON GAS CHASE TO RANGE

MECHANICAL PLANS:

1. GAS APPLIANCES SHALL COMPLY WITH CHAPTER 17 COMBUSTION AIR REQUIREMENTS. DETAIL HOW.
USE 1994 U.M.C. -IRC 2000 NOT ADOPTED FOR THIS SECTION

2. SHOW SIZE OF RETURN AND SUPPLY DUCTING TO FIRST BRANCH

ELECTRICAL PLANS:

1. DESIGNATE THE LOCATION AND CIRCUIT OF ALL REQUIRED LIGHT FIXTURES, RECEPTACLE OUTLETS, POWER
OUTLETS AND SWITCHES. PROVIDE A PANEL SCHEDULE NOTING CIRCUIT NUMBER AND SIZE ALONG WITH A
GENERAL DESCRIPTION. CHECK SUB-PANEL SHED. WIRE SIZE- BRK SIZE-ALSO SERVAL LIGHT DO NOT HAVE A CIRCUIT #

2. LIGHTING IN DINING ROOM CIRCUIT 3 ? ALSO ON A/C


IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
REYES ARVAYO @ 791-5550 EXT. 1113
08/13/2002 GERRY KOZIOL WWM REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
08/13/2002 MONICA VALDEZ OUT TO CUSTOMER Completed