Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T02CM03328
Parcel: 121111730

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T02CM03328
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2002 REYES ARVAYO BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM03328
2ND REVIEW
PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

STRUCTURAL PLANS:

1. PROVIDE BRACING DETAILS AND NOTES FOR EXTERIOR FRAME WALLS AND MAIN CROSS-STUD PARTITIONS,
OR USE FULLY BRACED, PER R602.10.3. A MINIMUM PANEL WIDTH OF 48" IS REQUIRED TO EFFECTIVELY
BRACE THE PARTITION. SEE TABLE R602.10.3, CATEGORY "C". IF BRACING DOES NOT COMPLY, PROVIDE A
LATERAL ANALYSIS OR ALTERNATE DESIGN TO BE REVIEWED BY THE PLANS EXAMINER. WIND FORCES
FOR SINGLE STORY RESIDENCES SHALL USE 90 MPH, EXPOSURE "B ---MIN 2'-8" BRACE PANEL-

IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
REYES ARVAYO @ 791-5550 EXT. 113

Final Status

Task End Date Reviewer's Name Type of Review Description
08/19/2002 MONICA VALDEZ OUT TO CUSTOMER Completed