Permit Review Detail
Review Status: Stopped
Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Permit Number - T02CM03140
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Stopped
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/01/2002 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 07/01/2002 | PETER MCLAUGHLIN | NPPO | REVIEW | Passed | |
| 07/01/2002 | BLANCA ESPINO | FLOODPLAIN | REVIEW | Approved | |
| 07/12/2002 | TERRY STEVENS | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN CHECK COMMENTS - PROJECT #T02CM03140 7/10/02 PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN. GENERAL REQUIREMENTS: 1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS. 2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. SITE PLAN: 1. INDICATE THE LOCATION OF GAS, WATER, ELECTRIC AND SEWER OR SEPTIC LINE ON THE PROPERTY, AND WHERE THEY ENTER THE BUILDING. PROVIDE THE LOCATION OF YOUR WATER METER AND SEPTIC SYSTEM IF IT EXISTS.----------IT APPEARS EXISTING GAS LINE WILL BE UNDER NEW ADDITION, MUST BE RELOCATED. IT APPEARS WATER LINE TO HOUSE IS BEING RELOCATED, NOT INDICATED ON PLUMBING PLAN. FOUNDATION PLANS: 1. FOR YOUR INFORMATION---------HOLD DOWNS ON THIS ADDITION ARE NOT REQUIRED BECAUSE OF THE ENTIRE BUILDING BEING SHEATHED THUS MEETING THE BRACED WALL DESIGN 2. FOOTING WIDTHS FOR ONE-STORY, PER TABLE R403.1: - 19" MINIMUM; FOR WOOD FRAME WITH VENEER STRUCTURAL PLANS: 1. DETAIL 7/6 INDICATES VENEER BEING SUPPORTED ON THE ROOF OF THE PORCH-------NOT ALLOWED. ALSO THERE IS NO WAY TO PROVIDE EDGE NAILING AT WALL FOR ROOF DIAPHRAGM. PLUMBING PLANS: 1. GAS: PROVIDE THE LENGTH OF LINE TO EACH APPLIANCE, BTU DEMAND OF EACH APPLIANCE, SIZE OF EACH BRANCH, TOTAL DEMAND & TOTAL DEVELOPED LENGTH FROM METER TO MOST REMOTE APPLIANCE ON THE SYSTEM PER UPC 1217.2----------NOTE: TYING INTO EXISTING GAS SYSTEM WILL REQUIRE A COMPLETE GAS PLAN FOR THE ENTIRE HOUSE. 2. WATER LINE: PROVIDE TOTAL FIXTURE DEMAND & MAXIMUM DEVELOPED LENGTH FOR THE ENTIRE HOUSE------NEW WATER LINE BEING INSTALLED FROM METER TO HOUSE AS PER SITE PLAN. PROVIDE SIZE AND LOCATION ON PLUMBING PLAN 3. THE CITY OF TUCSON HAS NOT ADOPTED THE PLUMBING SECTION OF THE IRC 2OOO. THE CURRENT CODE BEING USED IS THE 1994 UPC WITH THE STATE AMENDMENTS. ALL PLANS MUST REFERENCE TO THIS CODE. ELECTRICAL PLANS: 1. THE PANEL SCHEDULE INDICATES THAT THE WASHER AND DRYER ARE BEING RELOCATED. THIS IS NOT INDICATED ON THE PLUMBING, FLOOR, OR ELEC. PLANS--------CLARIFY IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: TERRY STEVENS @ 791-5550 EXT. 112 |
| 07/15/2002 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/15/2002 | ELAINE ROSE | REJECT SHELF | Stop |
| 07/01/2002 | ANY | APPROVAL SHELF | Stopped |
| 07/01/2002 | ANY | OUT TO CUSTOMER | Stopped |