Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T02CM03080
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/20/2002 | DAVE WITT | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN CHECK COMMENTS - PROJECT #T02CM03080 8/20/02 ( 2nd comments ) 3331 E. ELIDA ST. PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN. SCOPE OF REVIEW: THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL. GENERAL REQUIREMENTS: 1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS. 2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. FLOOR PLANS: 1. CHECK THE RESTRICTIONS ON WATER HEATER LOCATIONS IN U.P.C. SECTION 511.0 . STRUCTURAL PLANS: 1. HEADERS APPEAR INADEQUATE . 2. 4X8 APPEARS INADEQUATE AT THE CARPORT BEAM . 3. YOU HAVE SPEC'D A "CC46" AS THE 4X12 TO 8X8 CONNECTION. DO YOU MEAN A "CC48" ? SECTIONS - DETAILS - MISC. NOTES: 1. PROVIDE A CONNECTION FOR THE BEAM/COLUMN IN DETAIL D-D/5 . ( HARDWARE ) PLUMBING PLANS: 1. ELIMINATE THE GAS LINE TO THE ELECTRIC WATER HEATER . 2. WATER LINE: PROVIDE A WATER DISTRIBUTION DRAWING . 3. THE NEW FLOOR DRAIN IN THE LAUNDRY ROOM REQUIRES A TRAP AND A TRAP PRIMER OR DRAIN IT OUT SIDE . 4. THE DRAINS AND WASTE LINES DON'T APPEAR TO BE CONNECTED TO THE VENTS . ( SEE BATH #3 ) IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: DAVE WITT @ 791-5550 EXT. 1110 |
| 08/27/2002 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/29/2002 | DELMA ROBEY | OUT TO CUSTOMER | Completed |