Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Permit Number - T02CM03080
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/25/2002 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 06/25/2002 | MICHAEL ST. PAUL | NPPO | REVIEW | Passed | |
| 07/10/2002 | DAVE WITT | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN CHECK COMMENTS - PROJECT #T02CM03080 8/5/02 3331 E. ELIDA ST. PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN. SCOPE OF REVIEW: THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL. GENERAL REQUIREMENTS: 1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS. 2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. FLOOR PLANS: 1. CHECK THE RESTRICTIONS ON WATER HEATER LOCATIONS IN U.P.C. SECTIONS 510.2 AND 511.0 . 2. IS A WINDOW PARTIALLY IN THE BATHROOM #3 AND PARTIALLY IN THE WATER HEATER AREA? STRUCTURAL PLANS: 1. THE SLOPE OF THE RAFTERS OVER THE DINING ROOM IS 6:12 ON THE FRAMING PLAN WHICH APPEARS TO CONFLICT WITH 4:12 IN SECTION B-B . 2. THE RIDGE AS SHOWN IN SECTION B-B SHOULD BE 2X8 FOR THE2X6 RAFTERS . 3. PROVIDE MANUFACTURER'S CALCULATIONS AND DATA FOR PRE-FAB TRUSSES. TRUSS CALCULATIONS MUST BE SIGNED, DATED AND WET-SEALED BY AN ENGINEER WHO IS REGISTERED IN ARIZONA. TRUSS CALCULATIONS SHALL BE CROSS-REFERENCED TO THE FLOOR PLANS. 4. PLEASE NOTE , IN SECTION B-B , THE COLLARS ARE TO NOT BE IN THE TOP 1/3 OF THE ROOF FRAMING . 5. SPECIFY THE CONNECTIONS OF THE NEW 2X6 SUPPORT @ 4` c.c. TO THE EXISTING ROOF AND TO THE PROPOSED ROOF AS SEEN IN SECTION B-B . 6. HEADERS APPEAR INADEQUATE . 7. 4X8 APPEARS INADEQUATE AT THE CARPORT BEAM . 8. JUSTIFY THE 2X6 PONY WALL IN LIEU OF A BEAM FROM THE COLUMN TO THE WALL FOR THE CARPORT RAFTERS @ THE EXISTING ENTRY . DESCRIBE THE CONNECTIONS . SECTIONS - DETAILS - MISC. NOTES: 1. DETAIL 2/2 , IS THE STUCCO ON O.S.B.? HOW WILL THESE COLUMNS BE BRACED LATERALLY? 2. THE 8" ANCHOR BOLT WON`T AFFORD THE 7" INTO THE CONCRETE REQUIRED BY THE CODE. SEE DETAIL 2/2 . 3. IN SECTION A-A THE REFERENCED DETAIL FOR THE CARPORT BEAM IS DETAIL D-D/3 ; SHOULD THIS REFERENCE BE D-D/5 ? 4. PROVIDE A CONNECTION FOR THE BEAM/COLUMN IN DETAIL D-D/5 . 5. PROVIDE VENTILATION CALCULATIONS FOR THE VARIOUS ATTIC SPACES AND ILLUSTRATE . PLUMBING PLANS: 1. WATER HEATERS REQUIRE NOT LESS THAN 100 SQ.IN. OF FREE COMBUSTION AIR AND RELIEF AIR . 2. BATH #3 REQUIRES AN EXHAUST FAN . 3. GAS: IF YOU INCLUDE THE VERTICAL MEASUREMENTS IN THE LENGTH OF THE GAS LINE THE T.D.L. IS APROX. 55FEET. THE SIZES YOU'VE SPECIFIED ARE GOOD EXCEPT FROM THE GAS METER TO THE FIRST "T" WHICH SHOULD BE 1 ¼ INCHES. 4. WATER LINE: PROVIDE A WATER DISTRIBUTION DRAWING. 5. THE NEW FLOOR DRAIN IN THE LAUNDRY ROOM REQUIRES A TRAP , A TRAP PRIMER , AND AVENT WITH IN 5 FEET OR PLUMB IT TO THE OUTSIDE. 6. THE DRAINS AND WASTE LINES DON`T APPEAR TO BE CONNECTED TO THE VENTS. MECHANICAL PLANS: 1. NOTE ON PLANS: MECHANICAL SHALL COMPLY WITH CHAPTERS 12 - 24 2000 IRC. 2. BATH #3 REQUIRES AN EXHAUST FAN IF THE WINDOW IS LESS THAN 3 SQUARE FEET WITH HALF OPENING. ELECTRICAL PLANS: 1. NOTE ON PLANS: ELECTRICAL WORK SHALL COMPLY WITH CHAPTERS 33 - 42, 2000 IRC. 2. ANY WALL 2 FEET WIDE OR WIDER REQUIRES A RECEPTACLE. (BED ROOM #3, BETWEEN THE ENTRANCE DOOR AND THE BATH DOOR ) 3. THE MASTER BATH RECEPTACLES ON CIRCUITS 16 AND 1 REQUIRE G.F.C.I. PROTECTION. 4. THE PROPOSED PANEL SCHEDULE SHOWS CIRCUIT 9 AS A30 AMP IN THE DINING ROOM………? 5. WHICH CIRCUIT IS THE RECEPTACLE BY THE WATER HEATER IN BATH ROOM #3 ON. 6. THE A/C ISN`T REFLECTED IN THE PROPOSED LOAD CALCULATIONS. MODEL ENERGY CODE: 1. PROVIDE ENERGY CALCULATIONS PER THE 1998 IECC, OR COMPLY WITH IRC CHAPTER 11. 2. CALL OUT ON THE PLANS THE "R" VALUES OF INSULATION, AS WELL AS THE "U" VALUES OF THE WINDOWS AND DOORS IN CONFORMANCE WITH THE ENERGY CALCULATIONS PROVIDED. IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: DAVE WITT @ 791-5550 EXT. 110 |
| 07/11/2002 | PAUL MACHADO | FLOODPLAIN | REVIEW | Approved | |
| 08/07/2002 | MVALDEZ1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/07/2002 | LISA LESNY | OUT TO CUSTOMER | Completed |