Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T02CM03020
Parcel: 117141030

Address:
340 S STONE AV

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T02CM03020
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/27/2002 JIM EGAN FIRE REVIEW Approved
10/03/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing 1. Provide screens for the overflow roof drains, showin detail 5/A7.
10/03/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical 1. Model Energy Code calculations not with plan set. 2. Condensate line shall increase to 1" after second unit is attached to the line.
10/03/2002 HOLLY PEARCE WATER REVIEW Approved
10/09/2002 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied 1. Structural Calculations to utilize the 2000 IBC per adopted ordinance by the City of Tucson. See masonry wall design

2. A portion of the structural calculations use soil bearing pressures exceeding 1500 psf. Revise calculations or provide a soils report for this project reflecting soil bearing pressures used.

3. Sheet A5 indicates ceiling height to be 7' plus in height with a 8" box beam encroachment. The minimum height allowed in occupied spaces is 7'6". Reference sections 1207.2 and 1207.2.1 of the IBC. Please clarify actual heights.

4. Sheet A4 indicates use of panic hardware on an exit door opening inward. Please clarify.

5. Proposed steel lintel varies in size and length from structural details 203/204 and structural calculations. Please clarify.
10/17/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied Please return the plans I have already reviewed along with your next submission.

1) The entire plan including print must be a minimum of 1/8" or 10 point.

2) Provide fixture cuts for fixtures G and F. Please note F fixture must have a minimum efficiency of 45 lumens/watt.


3) Provide IECC light budget calculations for the interior.
USE PERMITTED W/FT2 AREA FT2 WATT/FT2 TOTAL ACTUAL
Banking 2 1689 3,378 Connected Watts
Office 1.8 100 180
RR .8 128 102
Storage 1 78 78
Lounge 1.8 260 468
Corridors 08 215 172
2,470 4,378 5,346

4) The service design is indicated to be existing. Please clarify.
10/28/2002 GERRY KOZIOL WWM REVIEW Approved
10/29/2002 JAMES TATE FLOODPLAIN REVIEW Denied A copy of the approved Site Plan must be included with the submittal.
10/30/2002 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
10/30/2002
Building plans may not be reviewed until the site plan is approved.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/01/2002 TAMI ACHONG OUT TO CUSTOMER Completed