Permit Number: T02CM03020
Parcel: 117141030

Address:
340 S STONE AV

Review Status: Completed

Review Details: SITE

Permit Number - T02CM03020
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/12/2002 JIM EGAN FIRE REVIEW Approved
09/18/2002 DAVID RIVERA HANDICAP-SITE REVIEW Approved
09/18/2002 DAVID RIVERA ZONING REVIEW Denied As of this review date September 18, 2002 it is not clear when the removal of the billboard will occur. I have forwarded the documents regarding the removal of the billboard to the City Attorney Frank Kern for his review and response. Pending the review and approval of the documents I have denied the latest site plan submittal. As soon as I have confirmation from the City Attorney's office regarding the billboard I will contact the Architect of record Paul O'Conner.
09/30/2002 ANY SANITATION REVIEW Approved
09/30/2002 PAUL MACHADO ENGINEERING REVIEW Denied To: Paul O'Connor, A.I.A.
Architect

SUBJECT: 340 N. Stone Ave.,
Site plan T02CM03020 (Third Review)
T14S, R15E, Section 28


RESUBMITTAL REQUIRED: Site Plan

The Site Plan (SP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Site Plan:

1. Scuppers for the roof drains at the west side of the buildings are also required. The scupper at the NW corner of the property is in the public right-of-way and will a separate permit COT Transportation. Contact the Department of Transportation at (520) 731-4249.
2. List estimated cut and fill quantities per D.S. 2-02.2.1.17. If both are 0 cy, please indicate by calling it out on the plans or a general note listing the same. Per previous comment.
3. Show existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number. Per previous comment.
4. Add to general notes: "Maximize water harvesting by depressing landscaped areas a maximum 6".



If you have any questions, I can be reached at 791-5550 or pmachad2@ci.tucson.az.us
Paul Machado, Senior Engineering Associate,
09/30/2002 ANY FLOODPLAIN REVIEW Approved
10/01/2002 JOE LINVILLE LANDSCAPE REVIEW Approved
10/01/2002 JOE LINVILLE NPPO REVIEW Approved SEE REVIEW OF 7/18/02

Final Status

Task End Date Reviewer's Name Type of Review Description
11/01/2002 TAMI ACHONG OUT TO CUSTOMER Completed