Permit Number: T02CM02974
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T02CM02974
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/21/2002 JIM EGAN FIRE REVIEW Approved
06/21/2002 TOM CLARK WATER REVIEW Approved
07/08/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical 1. Show on the plan how the mechanical design complies with Chapter 4 IMC 2000. 2. Provide the size of the condensate and overflow drain lines on the plan. 3. Comply with Sec 606.2 IMC 2000.
07/08/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing 1. Provide a civil site plan with FFE of the building and UP stream MH Rim elev.
07/10/2002 DOUG WILLIAMS FLOODPLAIN REVIEW Denied FFE should match the stamped/approved Site Plan
07/10/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied E1.0
1) It appears transformer TF lacks proper work clearance. 99NEC 110-26
2) It is not possible to evaluate the adequacy of the pole base without details about the pole and luminare.
E2.0
1) 1998 IECC requires dual switching resulting in a uniform reduction of the lighting in all areas except for the bathrooms and storage rooms.
E3.0
1) Bond the (N), (G) and transformer case. 99NEC 250-24
2) It appears the equipment bonding wire in the secondary feeder serving panel 'L1' should be increased in size to a #4 copper. 99NEC 250-102(c ).
3) Please clarify the feeder size serving switchboard MC. In addition, provide MC ampacity.
4) Please provide IECC calculations. Please note a maximum of .9w/ft2 is allowed for the entire facility. As an option you may utilize 1w/ft2 for the exercise area, .8w/ft2 for the restrooms and 1w/ft2 for the storage areas.
07/29/2002 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Denied See comments.
08/06/2002 MICHAEL ST. PAUL ZONING REVIEW Denied Building approvals required.
08/06/2002 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/23/2002 CINDY AGUILAR OUT TO CUSTOMER Completed