Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T02CM02912
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/11/2002 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Approved | Mechanical 1. Vents are not shown down stream of the condensate traps. Screens should not be used. 2. The equipment pads are to be 6" above grade. 3. Fire/Smoke dampers still not indicated on the plans for the corridors. 4. Transfer of air from a rated corridor to another space does not comply with Sec601.2IMC2000 andSec1004.3.2.4IBC 2000 Excp.1 is not being complied with. |
| 10/11/2002 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Approved | Plumbing 1. Indicate the 4X6X3 on P6 where the change takes place and indicate 6" waste down stream. 2. Incorrect use of a fitting, detail 10/P4. This fitting is not to be used on its side. |
| 10/14/2002 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approv-Cond | |
| 10/28/2002 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Approved | Worked with Jim Dove of Project Solutions to resolve outstanding NEC issues. Required that the plans be sent back Columbia, MO for revisions and appropriate EE stamps and signatures on 10/16/2002. Received them back on 10/25/2002. |
| 10/30/2002 | PATRICIA GEHLEN | ZONING | REVIEW | Approved | Zoning 10/30/2002 Copies of the stamped approved development and landscape plans must be included in the building plans prior to review and approval |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/03/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 06/03/2004 | TAMI ACHONG | REJECT SHELF | Completed |
| 11/01/2002 | ELAINE ROSE | APPROVAL SHELF | Completed |