Permit Number: T02CM02912
Parcel: 137341410

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T02CM02912
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/11/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Approved Mechanical 1. Vents are not shown down stream of the condensate traps. Screens should not be used. 2. The equipment pads are to be 6" above grade. 3. Fire/Smoke dampers still not indicated on the plans for the corridors. 4. Transfer of air from a rated corridor to another space does not comply with Sec601.2IMC2000 andSec1004.3.2.4IBC 2000 Excp.1 is not being complied with.
10/11/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Approved Plumbing 1. Indicate the 4X6X3 on P6 where the change takes place and indicate 6" waste down stream. 2. Incorrect use of a fitting, detail 10/P4. This fitting is not to be used on its side.
10/14/2002 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approv-Cond
10/28/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Approved Worked with Jim Dove of Project Solutions to resolve outstanding NEC issues. Required that the plans be sent back Columbia, MO for revisions and appropriate EE stamps and signatures on 10/16/2002. Received them back on 10/25/2002.
10/30/2002 PATRICIA GEHLEN ZONING REVIEW Approved Zoning
10/30/2002
Copies of the stamped approved development and landscape plans must be included in the building plans prior to review and approval

Final Status

Task End Date Reviewer's Name Type of Review Description
06/03/2004 TAMI ACHONG OUT TO CUSTOMER Completed
06/03/2004 TAMI ACHONG REJECT SHELF Completed
11/01/2002 ELAINE ROSE APPROVAL SHELF Completed