Permit Number: T02CM02912
Parcel: 137341410

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T02CM02912
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/30/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Minimum print for plans is 10pt. Mechanical 1. Show on the plan how the mechanical design complies with Chapter 4IMC2000. 2.Condensate drains shall comply with Sec 307.2.1IMC2000-No screens- provide a vent down stream of the traps. 3.Equipment set on concrete pads shall be 6" above grade-Sec 304.8IMC2000. 4.Provide Fire/Smoke dampers at all rated corridor openings. 5.Transfer of air form a rated corridor to another space does not comply with Sec601.2IMC2000. 6.Provide an engineered design for the dryer duct work and sizing. 7.Minimum EER for ( PTAC ) units is 10.0 per 1998 IECC.
07/30/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Minimum print size for plans is 10pt. Plumbing 1.Provide size of HCS 6" sewer is tapping into on the plan C-4.1. 2.Building waste line at the ninth tree shall be 6" -4X6X3. 3.Wet venting of the shower at the lav & ks shall be a min. of 2 1/2" not 2". 4.Venting of the wc is incorrect, vent shall not be up stream and down stream in the public toilets. Mop sink is not vented. 5.Mop sink, laundry tub and service sink require a clean out. 6.Provide trap primers for the floor drains Sec 1007.0UPC1994 Az. Code. 7.Provide total length of gas line on the plan and provide the the size of the line between the meter and the first branch. 8.Provide a water demand calculation based on Appendix 'A' UPC1994 Az. Code on the plan. 9.T&P on the water heaters shall discharge to the exterior of the building. 10.The expansion tank shall be installed on the CW side down stream of the check valve. 11.Combustion and venting of the water heaters in PVC in the trash shaft does not comply with Sec707.13.1IBC2000.
08/20/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
GENERAL COMMENTS
1) All print and symbols must be a minimum 10 point or 1/8". This is necessary for micro fiche.
2) See the red line set in addition to written comments for further clarification.
3) Please return the redline set along with your next submission. This will assist in my second review.
SPECIFICATION DOCUMENT
1) Page 16050-8 paragraph L #2. This sentence implies the wire under the pavement such as a parking lot does not need to be at least +24" deep. See 99NEC Table 300-5 and revise specification as required.
2) Page 16130-4 3.2 A. This specification requires conduit underground however UF is specified on the plan. Clarify on the plan and in the specification what wiring methods are allowed for both interior and exterior.
E1
1) It appears the circuitry for pole lights should be HP1-32,34. See page E8.
2) It appears the ground wire size described by General note 5 must be increased to a minimum #8 copper. 99NEC 250-122
E2, E3, E4
1) All exit and emergency light must connect to the unswitched side of the lighting circuit serving the area. 99NEC 700-12(e)
E2
1) The light in the elevator equipment room must be on the same circuit as the receptacle (HP1-24). The light should be connected to the line side of the GFCI
2) The dry pipe compressor specified by General note 8 does not appear in panel HP1.
3) All exterior lights must have a minimum efficacy of 45 lumens per watt. This is typical of types C, D. See page E5 for fixture types . See IECC 705.5.
4) 99NEC 620-22 requires one circuit per elevator to serve the elevator lighting. See general note 13.
5) 2000IBC 1003.2.11.2(4) requires emergency lighting on the exterior exit discharge immediately adjacent to the exit discharge.
E5
1) Provide the conductor size for the range.
2) 99NEC 210-8(a)(6) requires receptacles above the peninsular counter top for both units A and B (circuit 7) be GFCI protected.
E6
1 Taps to the 30 and 20 HP elevators require a minimum #4 copper ground. 99NEC250-122
2 99NEC 620-62 requires Selective Coordination for the elevators. Provide a coordination study. Utilize AFC on load side terminals of the elevator controllers.
3 99NEC 250-122(f)(1) requires #2 copper ground in each set of parallel feeders specified by note #3.
E7
1) It appears EF/2 connects to MP1-23 not HP1-1 as shown.
2) Both F2 and F5 are described as 120 V however on page E8 HP2-21,23 and 25,27 describes them as 208 v.
3) It appears EF3 should circuit to panel HP2-19 however it is not in the panel. See page E8
4) See comment E7 #2 above for F1 and F4. Disregard comment E8 #1 if F1 and F4 actually circuit to MP1-29,31-33,35 respectively.
5) See comment E7 #2 above for F3 and F6. On page E8 F3 and F6 circuit HP3-18,20-22,24 respectively.
E8
1) MP1-14 should read F/1 not spare as shown. See page E7.
09/12/2002 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied City of Tucson, Development Services
BUILDING AND STRUCTURAL COMMENTS


1) Provide safety glazing in glazed doors.
2) Specify the rise on stairs. Detail 9/A.12.1 refers to detail 4 but does not show the size
or height.
3) Specify thikness of plywood on treads at stairs.

4) Power operated doors sall comply with section 1003.3.1.3.2 which complies with
BHMA.A156.10.
5) Detail 17/S.8-clarify-does the upper chord of the truss project over the GLU-LAM
Beam ? Also, it appears that a plate appears over the upper chord of the truss, clarify.
09/18/2002 MICHAEL ST. PAUL ZONING REVIEW Needs Review Building approvals required.
09/18/2002 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/02/2002 MONICA VALDEZ OUT TO CUSTOMER Completed