Review Date Reviewer's Name Type of Review Description Status Comments
11/01/2002 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM02910

11/15/02 2101 E. WATER ST.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.



FOUNDATION PLANS:

1. NOTE ON THE DRAWINGS THE ALLOWABLE SOIL BEARING PRESSURE USED IN THE DESIGN OF THE FOOTINGS,
OR STATE THAT THE ASSUMED VALUE OF 1500 PSF IS BEING USED, PER TABLE R401.4.1, A SOILS REPORT IS
NOT REQUIRED. IT IS UP TO THE DESIGNER/HOMEBUILDER TO BE AWARE OF THE SOIL AND CONDITIONS OF
THE SITE. IF SOIL TESTING HAS BEEN DONE, A COPY OF THE SOILS REPORT SHALL BE SUBMITTED WITH THE
CONSTRUCTION PLANS, AND THE FOUNDATION DESIGN SHALL REFLECT THE SOILS REPORTS
RECOMMENDATIONS.

2. PROVIDE A FOUNDATION PLAN. SHOW FOOTING LOCATIONS, AND THE HOLD-DOWNS FOR THE BRACED WALL PANELS THAT ARE LESS THAN 4' WIDE.

3. THE MINIMUM FOOTING WIDTH FOR A FRAME WALL IS 16".

4. ALL FOUNDATION HOLD-DOWNS AND ANCHOR BOLT SPACING FOR SHEAR WALLS SHALL BE SPECIFIED AND
LOCATED.

FLOOR PLANS:

1. COMPLY WITH R309.2. PROVIDE ½" GYPSUM BOARD ON BOTH SIDES OF THE WALL COMMON TO THE GARAGE AND HOUSE.

2. LOCATE AND IDENTIFY SHEAR WALL TYPES AND LOCATIONS.

3. IDENTIFY CEILING HEIGHTS IN ALL AREAS ON FLOOR PLAN. IF SLOPED CEILING, NOTE AVERAGE HEIGHT.

STRUCTURAL PLANS:

1. SPECIFY LUMBER GRADE AND SPECIES. SPECIFY MANUFACTURER AND SERIES ON GLULAMS AND "I" JOISTS.

2. COMPLETELY DETAIL THE CONNECTIONS AND CROSS-REFERENCE TO THE FRAMING
PLAN. (RAFTER TO LEDGER AND LEDGER TO STUD)





ELEVATIONS:

1. SHOW THE LOCATIONS AND SIZE OF THE SCUPPERS. MAKE SURE VENTILATED CRICKETS ARE PROVIDED TO GUIDE THE WATER TO THE SCUPPERS.

SECTIONS - DETAILS - MISC. NOTES:

1. DETAIL THE SUSPENDED CEILING. HOW IS IT BUILT? HOW IS IT SUSPENDED? MATERIALS?

2. PROVIDE A BUILDING CROSS-SECTION. MORE THAN ONE MAY BE REQUIRED TO CLEARLY ILLUSTRATE HOW
THE STRUCTURE IS BUILT. SHOW THE FOOTING, THE ANCHOR BOLTS,PLATE, STUDS, WALL SHEATHING AND COVERINGS, LEDGER/STUD CONNECTION, RAFTER/LEDGER CONNECTION, ROOF DECKING AND ROOFING.

3. WOOD SILL PLATES SHALL BE FOUNDATION GRADE REDWOOD OR PRESSURE-TREATED WOOD PER R324.

4. NOTE AND SPECIFY ALL LEDGERS AND CONNECTIONS TO WOOD FRAME .

PLUMBING PLANS:

1. GAS: PROVIDE THE LENGTH OF THE GAS LINE FROM THE NEW GAS METER LOCATION TO THE MOST DISTANT GAS APPLIANCE. IT SHOULD BE THE SUM OF BOTH HORIZONTAL AND VERTICAL DISTANCES.

2. PROVIDE A LIST OF THE EXISTING GAS APPLIANCES AND THE INPUT RATING OF THE FURNACE (IF THE FURNACE IS GAS).

ELECTRICAL PLANS:

1. PROVIDE G.F.C.I. PROTECTION FOR THE WALL RECEPTACLES IN THE GARAGE.

2. NOTE THAT LIGHT FIXTURES IN CLOTHES CLOSETS SHALL BE INSTALLED IN ACCORDANCE WITH E3903.11.

3. NOTE THAT THE EXISTING SLEEPING AREAS ARE TO BE PROVIDED WITH SMOKE DETECTORS.




IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110
11/01/2002 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
11/01/2002 PATRICIA GEHLEN ZONING REVIEW Approved
11/01/2002 LLESNY1 NPPO REVIEW Passed