Permit Number: T02CM02896
Parcel: 141016740

Review Status: Completed

Review Details: SITE

Permit Number - T02CM02896
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/19/2002 MICHAEL ST. PAUL ZONING REVIEW Passed
06/19/2002 MICHAEL ST. PAUL NPPO REVIEW Passed
06/19/2002 MICHAEL ST. PAUL LANDSCAPE REVIEW Passed
07/17/2002 ANY FLOODPLAIN REVIEW Denied
07/17/2002 PAUL MACHADO ENGINEERING REVIEW Denied To: Swaim Associates
3986 E. Broadway Blvd. Attn.: Gal Winters



SUBJECT: Civano Comm. School 10603 E. Mira Lane
Site plan T02CM02896 (First Review)
T14S, R14E, Section 2


RESUBMITTAL REQUIRED: Site Plan.

The Site Plan (SP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Site Plan:

1. Show existing sight visibility triangles on Night Bloom Way and Mira Lane per 2-02.2.1.10.
2. List property description on plans per 2-02.2.1.1.
3. Please list estimated cut & fill quantities per D.S. 2-02.2.1.17.
4. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks. Please provide supporting calculations to demonstrate compliance with D.S 3-01.4.4.
5. Dimension from street monument lines and right-of-way etc. per D.S. 2-02.1.19.
6. Dimensions from street monument lines to existing and proposed curbs, S/W, utilities etc. per D.S. 2-02.2.1.21.
7. New sidewalk is required along both Night Bloom Way and Mira Lane. Match existing.
8. A separate permit is required for any work done in the right-of-way, call 791-4942 for additional information.
9. Add to general notes: Depress all landscaped areas a maximum of 6" for water harvesting.
10. Show location and access of refuse container per D.S. 6-01.
11. General note 5 on sheet x1.2 refers to the Pima County Zoning code, this note should read that all work shall conform to 2000 IBC.

If you have any questions, I can be reached at 791-5550 or pmachad2@ci.tucson.az.us
07/17/2002 ANY SANITATION REVIEW Denied
07/18/2002 JIM EGAN FIRE REVIEW Approv-Cond 1.FIRE APPROVAL FOR SITE ONLY.
2. FIRE HYDRANT SHALL BE INSTALLED AND IN-SERVICE BEFORE CONSTRUCTION BEGINS.
3.ON STREET PARKING IS NOT PERMITTED EXCEPT IN DESIGNATED SPACES.
07/18/2002 PATRICIA GEHLEN HANDICAP-SITE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/31/2002 TAMI ACHONG OUT TO CUSTOMER Completed