Permit Number: T02CM02876
Parcel: 117023640

Address:
934 N MAIN AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T02CM02876
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/12/2002 ANY FLOODPLAIN REVIEW Approved
06/17/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Approved
06/17/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical 1. Condensate discharge shall comply with Sec 307.2.1 IMC 2000. 2. Provide a Type-I hood per Sec507.2.2 IMC 2000- Architect to provide a complete details for a one hour chase. 3. Provide make-up air per Sec 508.1 IMC 2000.
06/19/2002 JIM EGAN FIRE REVIEW Approved
06/20/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Approved
07/16/2002 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied City of Tucson, Development Services
BUILDING AND STRUCTURAL COMMENTS


1) PROVIDE A DETAIL OF CONNECTION OF NEW PARTITION TO ROOF IN
THE PARALLEL CONDITION AND IN THE PERPENDICULER CONDITION.
SPECIFY SIZE AND TYPE OF CONNECTOR.
07/19/2002 GERRY KOZIOL WWM REVIEW Approved
07/19/2002 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
07/19/2002
See comments on the card
The DSMR information must be added to sheet A1.0 (case number, date of approval, modification granted, and conditions imposed).
07/19/2002 TOM CLARK WATER REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/22/2002 LISA LESNY OUT TO CUSTOMER Completed