Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T02CM02854
Parcel: 14016003F

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T02CM02854
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/12/2002 JIM EGAN FIRE REVIEW Approved
07/03/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied SEE T02CM02851
07/03/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied SEE T02CM02851
07/09/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied GENERAL COMMENTS
1) Please return the plans I have already reviewed along with your second submittal. This requirement is essential in expediting the 2nd review.
2) Please reference the originally reviewed plans for additional information and lighting budget calculations.
E1
1) The structural plans do not show pole base design as indicated on the plan.
2) Provide fixture cuts for SA and SB. Please note COT ordinance prohibits any uplight.
3) General note #1 specifies 1996 NEC, it should read 1999 NEC.
ADMINISTRATION
E2
1) Except for the bath, corridor, and lobby areas all lighting is required to be switched such that you can achieve a uniform reduction of the lighting load by 50% per 1998 IECC 705.2.1.
2) Provide IECC interior lighting budget calculations. See the plans I originally reviewed for proposed calculations.
3) Provide fixture cuts for the type G fixture.
E5
1) The utility published available fault current is 55,600 amps for this size service. My measurements indicate the linear distance to panel A is approximately 170' maximum, therefor F1 is approximately 9,719 amps.
2) It appears your notes stipulate a series rated system based on a 42/10 kAIC system which is not adequate. In addition, panels B1, B2, and C indicate a 22/10kAIC system. Please modify the notes utilizing the corrected utility fault current.
BUILDING B
E4
1) See comments ADMINISTRATION, E2, #1, #2 and #3 above.
2) Provide circuit number and load for type H fixtures.
E5
1) It appears the maximum feeder length for panels B1 and B2 is 20', therefor F2 and F3 are approximately 35,747 amps.
BUILDING C
E4
1) See comments ADMINISTRATION, E2, #1, #2, and #3 above.
2) Provide circuit number and load for type H fixtures.
E5
1) Based upon 55,600 amps of fault current F4 fault to panel C is approximately 12,359 amps.
BUILDING D
E4
1) See comments ADMINISTRATION, E2, #1, #2, and #3 above.
2) Provide circuit number and load for type H fixtures.
E5
1) The length of D1 feeder appears to be approximately 120' long, therefore F5 fault is approximately 12,834 amps.
07/24/2002 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied
07/31/2002 MICHAEL ST. PAUL ZONING REVIEW Needs Review Building approval required.
08/05/2002 PAUL MACHADO FLOODPLAIN REVIEW Approved
08/05/2002 TOM CLARK WATER REVIEW Approved
08/05/2002 GERRY KOZIOL WWM REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
08/07/2002 TAMI ACHONG OUT TO CUSTOMER Completed