Permit Number: T02CM02829
Parcel: 126162870

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM

Permit Number - T02CM02829
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/10/2002 PATRICIA GEHLEN ZONING REVIEW Approved
06/10/2002 PATRICIA GEHLEN NPPO REVIEW Passed
06/10/2002 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
09/11/2002 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM02829

9/10/02 4002 E. CALLE CHICA

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

FOUNDATION PLANS:

1. FOOTING WIDTHS FOR ONE-STORY, PER TABLE R403.1 ( 19" FOR SINGLE STORY, 4"BRICK VENEER ON LIGHT FRAME )

FLOOR PLANS:

1. LABEL ALL ROOMS AND SPACES. SHOW ALL DOORS. SHOW ENTIRE FLOOR PLAN.

2. PROVIDE THE LOCATIONS OF TEMPERED GLASS PER R308.4. (DOOR "D", WINDOWS "G" & "H")

3. PROVIDE ACCESS TO EACH SEPARATE ATTIC AND CRAWL SPACE THAT EXCEEDS 30SF. DESIGNATE
LOCATIONS ON THE DRAWINGS. OPENINGS SHALL NOT BE LESS THAN 22" BY 30". THE ATTIC ACCESS SHALL
PROVIDE A MINIMUM OF 30" OF HEADROOM, AND SHALL BE LOCATED IN A READILY ACCESSIBLE SPACE PER R807.

4. IDENTIFY CEILING HEIGHTS IN ALL AREAS ON FLOOR PLAN. IF SLOPED CEILING, NOTE AVERAGE HEIGHT.

STRUCTURAL PLANS:

1. WHAT SUPPORTS THE MULTIPLE 2X4 POSTS (KEYNOTE #6 ) OTHER THAN THE PROPOSED GARAGE DOOR HEADER ?

2. OVER FRAMED AREAS: IF SOLID SHEATHING IS USED ON THE LOWER TRUSSES, PROVIDE
MINIMUM OPENINGS OF 22" BY 30" FOR ACCESS AND VENTILATION INTO OVER FRAMED AREAS (>30 S.F.). IF
SOLID SHEATHING IS NOT USED ON LOWER TRUSSES, PROVIDE DETAILS FOR BRACING OF TOP CHORD OF
LOWER TRUSSES.

3. PROVIDE A DETAIL FOR THE RAFTER TO RIDGE CONNECTION.

4. NOTE JOIST HANGERS BY TYPE AND SIZE.

5. JUSTIFY THE EXISTING RAFTERS' CAPABILITY TO SUPPORT THE PROPOSED RIDGE BEAMS. IS CONNECTIVE HARDWARE NEEDED FOR THE BEAM/HEADER AND HEADER/RAFTER ?




ELEVATIONS:

1. NOTE AND SPECIFY ALL ROOF SLOPES APPROPRIATE TO MATERIAL (SEE R905).

2. SHOW CALCULATION OF ATTIC VENTILATION AREA IN COMPLIANCE WITH R806.2. NOTE LOCATION OF ALL
VENTS NEEDED TO COMPLY.

3. NOTE GLASS IN HAZARDOUS AREAS SHALL BE SAFETY GLASS PER R308.4.

SECTIONS - DETAILS - MISC. NOTES:

1. ON STANDARD DETAIL AND NOTE SHEETS, CROSS-OUT ALL DETAILS AND NOTES THAT DO NOT APPLY OR WERE NOT USED.

2. 1/A4 & 1/A5 , THE MINIMUM FOOTING WIDTH IS 19".

3. 1/A4 , SPECIFY THE FLASHING AND THE WEEP HOLES.

4. 1/A4 ,DESCRIBE THE 1" GROUT OR AIR SPACE BEHIND THE BRICK VENEER.

5. 1/A4 , DESCRIBE THE BOTTOM PLATE AND THE ANCHOR BOLTS.

6. 3/A4 , WHERE IS IT USED ? THE MASONRY WALL NEEDS A FOOTING.

7. PROVIDE A LINTEL SCHEDULE FOR A SINGLE WYTHE WALL.

8. THE AISC MANUAL OF STEEL CONSTRUCTION DOESN'T LIST A 6"X 31/2"X 1/4" ANGLE. PLEASE CONFIRM THE AVAILABILITY AND PROVIDE THE SECTION MODULOUS FOR THE GARAGE DOOR LINTEL.

9. A/5,IS KEYNOTE 10 A VALLEY RAFTER OR A PLATE ? IF IT'S A VALLEY RAFTER , PLEASE PROVIDE A DETAIL.

PLUMBING PLANS:

1. PROVIDE THE SIZE OF THE PROPOSED SEWER LINE.

2. THE PLUMBING NOTES SHOULD REFER TO THE '94 U.P.C. WITH THE STATE AMENDMENTS

3. PLUMBING FIXTURE SCHEDULE; CLOTHES WASHERS REQUIRE 6 UNITS OF WATER AND HOSE BIBS REQUIRE 3 UNITS.

4. PROVIDE THE EXISTING PLUMBING FIXTURE COUNT AND THE NEW TOTAL DEVELOPED LENGTH.

MECHANICAL PLANS:

1. NOTE ON PLANS: MECHANICAL SHALL COMPLY WITH CHAPTERS 12 - 24 2000 IRC.

2. SIZE THE RETURN AIR REGISTER.

3. IF THE HEATING OR AIR CONDITIONING EQUIPMENT IS LOCATED IN THE ATTIC, SHOW LOCATION OF ACCESS,
CATWALK AND WORKING PLATFORM. SHOW PROVISIONS FOR AND ROUTE OF SECONDARY CONDENSATE
DRAIN PER M1305.1.3.

ELECTRICAL PLANS:

1. NOTE ON PLANS: ELECTRICAL WORK SHALL COMPLY WITH CHAPTERS 33 - 42, 2000 IRC.

2. NOTE ON THE PLANS THAT THE RECESSED LIGHT IN THE SHOWER IS TO BE RATED FOR USE IN A WET LOCATION.

4. NOTE ON THE PLANS THAT THE EXISTING RESIDENCE IS TO BE EQUIPPED WITH SMOKE DETECTORS IN ACCORD WITH R317.1.1 .

4. A RECEPTACLE IS REQUIRED AT THE BACK OF THE HOUSE PER E3801.7 .IS ONE ALREADY EXISTING ?

5. INDICATE THE LOCATION OF CONVENIENCE OUTLET AND LIGHT SWITCH FOR ATTIC HEATING AND AIR
CONDITIONING EQUIPMENT PER E3801.11 AND E3803.4.

7. WHERE CEILING FANS ARE SHOWN ON THE PLANS, PROVIDE A NOTE INDICATING ONLY APPROVED
OUTLET BOXES SHALL BE USED, PER E4001.6.

8. PROVIDE AN ELECTRICAL RISER DIAGRAM.



IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110
09/11/2002 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/13/2002 MONICA VALDEZ OUT TO CUSTOMER Completed