Permit Number: T02CM02799
Parcel: 125075390

Address:
2216 E 7TH ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM

Permit Number - T02CM02799
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/12/2002 PATRICIA GEHLEN ZONING REVIEW Approved
07/12/2002 PATRICIA GEHLEN NPPO REVIEW Passed
07/12/2002 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
08/07/2002 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM02799

8/7/02 2216 E. 7TH ST.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.


FOUNDATION PLANS:

1. FOOTING WIDTH FOR MASONRY WALLS, PER TABLE R403.1, IS 19".


FLOOR PLANS:

1. PROVIDE A 1-HOUR WALL WHERE THE CARPORT IS LESS THAN 3 FEET FROM THE PROPERTY LINE.
THIS CREATES A GARAGE AND THE KITCHEN AND DINING AREA WINDOWS SHOULD BE ADDRESSED.

2. PROVIDE A HANDRAIL FOR THE NORTH STEPS, PER R315, AND DETAIL.

STRUCTURAL PLANS:

1. THE RIDGE BOARD OF THE TRUSSES, SEE THE TRUSS DIAGRAM AND THE ROOF FRAMING PLAN, IS REQUIRED TO COVER THE CUT END OF THE RAFTER.

2. THE 6X8 #2 DF APPEARS INADEQUATE FOR THE 11 FOOT SPAN AT THE SOUTH PORCH USING 5PSF D.L. AND 20PSF L.L. PROVIDE JUSTIFICATION.

3. THE 4X10 #2DF AT THE INTERIOR OPENING APPEARS INADEQUATE FOR THE 11.33 FOOT SPAN USING 78.5`/2 TRIBUTARY AREA @ 35PSF.

SECTIONS - DETAILS - MISC. NOTES:

1. SECTION A-A, SPECIFY THE ROOF SLOPE. SPECIFY THE ROOF SLOPE AND DECKING OR PURLINS AND LAP SEALANT PER R905.10 .

2. PROVIDE A "SPECIAL INSPECTOR" BY WAY OF A SPECIAL INSPECTION FORM.

3. DETAIL 2/4 , THE LEDGER BOLTS ARE SPEC`D @ 24" O.C. FOR 16" COLUMNS.

4. DETAIL 1/4 , DESCRIBE THE STRUT TO BLOCK AND THE BLOCK TO RAFTER CONNECTIONS.

5. DETAIL 4/4 , 16d @ 12" C.C. APPEARS INADEQUATE FOR THE LEDGER TO PLATE CONNECTION. 25psf(9.67`/2)=120plf @THE LEDGER

6. DETAIL AND NOTE ALL MASONRY WALL REINFORCEMENT PER R606.11.2.2.3.


PLUMBING PLANS:

1. NOTE AND SPECIFY ALL PIPING MATERIALS.

2. THE SHOWER HAS NO VENT , THE CLOTHES WASHER HAS NO DRAIN , TWO TRAPS ARE NOT PERMITTED ON ONE DRAIN LINE (LAVS. / SHOWER)

3. NOTE ON PLANS THAT SHOWER AND TUB / SHOWER COMBINATIONS THAT HAVE INDIVIDUAL CONTROL
VALVES SHALL BE OF THE PRESSURE BALANCE OR THERMOSTATIC MIXING VALVE TYPE.


ELECTRICAL PLANS:

1. WHERE CEILING FANS ARE SHOWN ON THE PLANS, PROVIDE A NOTE INDICATING ONLY APPROVED
OUTLET BOXES SHALL BE USED, PER E4001.6.

2. NOTE THAT LIGHT FIXTURES IN CLOTHES CLOSETS SHALL BE INSTALLED IN ACCORDANCE WITH E3903.11.





IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 110
08/13/2002 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/22/2002 TAMI ACHONG OUT TO CUSTOMER Completed