Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T02CM02717
Parcel: 124041000

Address:
845 N PARK AV

Review Status: Completed

Review Details: 3RD PARTY REVIEW-REVISION/OTHER-2ND

Permit Number - T02CM02717
Review Name: 3RD PARTY REVIEW-REVISION/OTHER-2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2004 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
General
1. Please clarify uses of Rooms 165, 164, 166, 263 as rooms used for equipment storage shall be constructed per IBC 302.1.1 and 302.1.1.1.

PLUMBING COMMENTS - The Plumbing portion has been reviewed and approved.

MECHANICAL COMMENTS
General
1. Coordinate with Architectural Comment 1 for fire/smoke dampers as appropriate.

ELECTRICAL COMMENTS
General
1. Please clarify the use of the space and address the following as applicable:
a. All antenna and radio distribution shall be listed as per NEC 300-21(a) products of combustion (b) plenum rated (c) installation and use.
b. All antennas and lead-ins shall be grounded as per NEC 250-50, 250-104(a) and 250-92(b).
c. All electrical discharge equipment shall be located outside of building. Ref. NEC 210-20(b) and 810.57.

2. Provide visual alarm for Reception 270. Ref. IBC 907.9.1.1.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/08/2004 ELAINE ROSE OUT TO CUSTOMER Completed