Review Details: 3RD PARTY REVIEW-REVISION/OTHER-2ND
Permit Number - T02CM02717
Review Name: 3RD PARTY REVIEW-REVISION/OTHER-2ND
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/08/2004 | GP | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Denied | ARCHITECTURAL COMMENTS General 1. Please clarify uses of Rooms 165, 164, 166, 263 as rooms used for equipment storage shall be constructed per IBC 302.1.1 and 302.1.1.1. PLUMBING COMMENTS - The Plumbing portion has been reviewed and approved. MECHANICAL COMMENTS General 1. Coordinate with Architectural Comment 1 for fire/smoke dampers as appropriate. ELECTRICAL COMMENTS General 1. Please clarify the use of the space and address the following as applicable: a. All antenna and radio distribution shall be listed as per NEC 300-21(a) products of combustion (b) plenum rated (c) installation and use. b. All antennas and lead-ins shall be grounded as per NEC 250-50, 250-104(a) and 250-92(b). c. All electrical discharge equipment shall be located outside of building. Ref. NEC 210-20(b) and 810.57. 2. Provide visual alarm for Reception 270. Ref. IBC 907.9.1.1. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/08/2004 | ELAINE ROSE | OUT TO CUSTOMER | Completed |