Review Details: 3RD PARTY REVIEW-REVISION/OTHER

Permit Number - T02CM02717
Review Name: 3RD PARTY REVIEW-REVISION/OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2004 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
General
1. Please revise ASK-0676 to reflect a 2-hr fire resistive enclosure for that portion of the Elevator Shaft Vent Duct that is not within the hoistway shaft and not within the Elevator Machine Room. See Detail 01 where duct exits the shaft and turns 90° below the floor slab of the Machine Room. Ref. IBC 3004.2, or since IBC does not require venting of hoistway in a sprinklered building it may be an option to request interpretation from the Building Office that the duct work penetrating the shaft is part of a smoke control system. Ref. IBC 707.8, 707.10, 715.52). Otherwise, a damper would be required at the penetration, however, such damper would defeat the purpose of the vent when/if damper was activated.

2. Please specify size of duct and louver in ASK-0676. Ref. IBC 3004.3.

ELECTRICAL COMMENTS
Sheets E102, E201 and E601
1. Indicate if Delta K is part of this revision (K is not shown under Delta Revisions).

2. Delta 15 is not shown in Delta Revision. Delta 15 appears to be a part of revision (add to all sheets).

3. Provide note to address service disconnect for fire pump service.

4. Provide proper grounding, bonding and common grounding electrode. Ref. NEC 250-50, 250-58, 250-90, 250-122 and 250-105(a)(3)(4).

Sheet E401
1. Remove diesel pump and revise room for electrical fire pump.

2. Indicate if Circuits LEM 13, 15 and HEM 8, 10 and 22 remain the same.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/05/2004 ELAINE ROSE OUT TO CUSTOMER Completed