Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T02CM02710
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/04/2002 | JIM EGAN | FIRE | REVIEW | Approved | |
| 06/04/2002 | MARK TITUS | WATER | REVIEW | Approved | |
| 06/07/2002 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | Mechanical 1. Provide the manufactures name and listing for the mechanical equipment per Sec301.4 thru Sec301.6 IMC 2000 on the plan. 2. Show on the plan how the Mech. design complies with Chapter 4 IMC 2000. NOTE: Is this a gas pack or a heat pump as the plan indicates. |
| 06/07/2002 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | Plumbing 1.Provide a civil site plan with the F.F.E. of the buildings , UP stream M.H. Rim elev. and slope of all sewers. 2. Provide a water demand calculation based on Appendix 'A' UPC1994 Az. Code on the plan. 3. Provide the manufactures name and listing for all plumbing fixtures on the plan, Sec301.1.1 UPC1994 Az. Code. |
| 06/11/2002 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | |
| 06/28/2002 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied | |
| 07/05/2002 | PATRICIA GEHLEN | ZONING | REVIEW | Denied | Se comments for T02CM02711. |
| 07/05/2002 | MSTPAUL1 | FLOODPLAIN | REVIEW | Needs Review | |
| 07/05/2002 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/10/2002 | TAMI ACHONG | OUT TO CUSTOMER | Completed |