Permit Number: T02CM02710
Parcel: 121120320

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T02CM02710
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/04/2002 JIM EGAN FIRE REVIEW Approved
06/04/2002 MARK TITUS WATER REVIEW Approved
06/07/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical 1. Provide the manufactures name and listing for the mechanical equipment per Sec301.4 thru Sec301.6 IMC 2000 on the plan. 2. Show on the plan how the Mech. design complies with Chapter 4 IMC 2000. NOTE: Is this a gas pack or a heat pump as the plan indicates.
06/07/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing 1.Provide a civil site plan with the F.F.E. of the buildings , UP stream M.H. Rim elev. and slope of all sewers. 2. Provide a water demand calculation based on Appendix 'A' UPC1994 Az. Code on the plan. 3. Provide the manufactures name and listing for all plumbing fixtures on the plan, Sec301.1.1 UPC1994 Az. Code.
06/11/2002 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied
06/28/2002 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied
07/05/2002 PATRICIA GEHLEN ZONING REVIEW Denied Se comments for T02CM02711.
07/05/2002 MSTPAUL1 FLOODPLAIN REVIEW Needs Review
07/05/2002 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/10/2002 TAMI ACHONG OUT TO CUSTOMER Completed