Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T02CM02690
Parcel: 126150250

Address:
4449 E COOPER ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM

Permit Number - T02CM02690
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/31/2002 PATRICIA GEHLEN ZONING REVIEW Approved
05/31/2002 PATRICIA GEHLEN NPPO REVIEW Passed
05/31/2002 ANY FLOODPLAIN REVIEW Approved
06/28/2002 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM02690

6/28/02 4449 E. COOPER ST.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.



FLOOR PLANS:

1. DOOR #2 , GARAGE / KITCHEN , IS REQUIRED TO BE SOLID CORE . LABEL ALL ROOMS AND SPACES.



PLUMBING PLANS:


1. GAS: PROVIDE THE EXISTING GAS LOAD AND THE TOTAL DEVELOPED LENGTH PER U.P.C. 1217.2

2. WATER LINE: PROVIDE TOTAL FIXTURE DEMAND & MAXIMUM DEVELOPED LENGTH

3. PROVIDE PRESSURE AND TEMPERATURE RELIEF VALVE AT WATER HEATER.


ELECTRICAL PLANS:

1. SPECIFY A BREAKER FOR THE SUB PANEL FEEDERS. ALTHOUGH YOU'VE PROVIDED 100 AMP CONDUCTORS, THE SUB PANEL AND GROUND ARE RATED AT 60 AMPS.

2. THE SUB PANEL A IS LOCATED IN THE STORAGE ROOM AND IS NOTED AS PANEL A ON THE POWER DIAGRAM AS PANEL A , BUT THE CIRCUITS APPEAR TO ORIGINATE IN A PANEL B .

3. READILY ACCESSIBLE RECEPTACLES IN THE GARAGE ARE REQUIRED TO BE GFCI PROTECTED .

4. WHERE CEILING FANS ARE SHOWN ON THE PLANS, PROVIDE A NOTE INDICATING ONLY APPROVED
OUTLET BOXES SHALL BE USED, PER E4001.6.

IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 110
07/01/2002 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/15/2002 MONICA VALDEZ OUT TO CUSTOMER Completed