Permit Number: T02CM02674
Parcel: Unknown

Address:
1021 N WILMOT RD

Review Status: Completed

Review Details: SITE

Permit Number - T02CM02674
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/28/2002 LAITH ALSHAMI ENGINEERING REVIEW Needs Review Laith Alshami, Floodplain and Engineering comments, 06/28/2002:

The submittal does not include a site plan for review nor does it have a site plan review card (yellow card).
06/28/2002 LAITH ALSHAMI FLOODPLAIN REVIEW Needs Review Laith Alshami, Floodplain Comments, 06/28/2002:

1- The submittal does not include a site plan for review nor does it have a site plan review card (yellow card).
2- The project is not in FEMA floodplain, however, it appears that Wilmot Road has a lot of runoff during the 100-year storm which may cause flooding problems to the subject site. A hydrology report is required to determine any flooding problems. Please be advised that based on the hydrology report conclusions, a floodplain use permit may be required.
07/02/2002 JIM EGAN FIRE REVIEW Approved
07/02/2002 PHIL SEADER HANDICAP-SITE REVIEW Denied
07/12/2002 LLESNY1 LANDSCAPE REVIEW Needs Review
07/12/2002 LLESNY1 NPPO REVIEW Needs Review
07/12/2002 DAN CASTRO ZONING REVIEW Approved COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.
CODE SECTION/ DEVELOPMENT STANDARD

1. The following comments are based on a less than 25% expansion of the building area.

2. Note the legal description.
D.S. 2-02.2.1.A.2

3. Note the proposed building height.
D.S. 2-02.2.1.A6

4. a) A 24 foot wide PAAL is required for the 90 degree parking spaces located west of the building. These parking spaces are not shown on the last approved site plan.
b) Dimension the wheelstop location for the west parking spaces. Wheelstops must be located two and one-half (2½0 feet in front of the parking space.
D.S. 2-02.2.1A.8/ D.S. 3-05.2.3.C.2

5. Dimension the width of the ingress/egress point.
D.S. 2-02.2.1.A.11

6. If applicable, provide a detail of proposed free- standing signage and outdoor lighting on the site plan.
D.S. 2-02.2.1A.13/ D.S. 2-02.2.1.A.25

7. Dimension the Wilmot Road existing and future ½ right-of-way and future curb location.
D.S. 2-02.2.1.A.19/ D.S. 2-02.2.1.A.21

8. Note the existing zoning classification for the subject property and adjacent parcel to the south on the site plan.
D.S. 2-02.2.1.A.28

9. Add the following note: "Proposed use: Food Service, development designator "30" subjcet to Sec. 3.5.4.6.C and 3.5.13.5."
D.S. 2-02.2.1.A.31

10. Note the gross site area.
D.S. 2-02.2.2.A.1

11. Note the floor area of the proposed building and if applicable, any outdoor dining area. Label and dimension any outdoor dining area on the site plan.
D.S. 2-02.2.2.A.2

12. Provide the floor area calculation for the overall site.
D.S. 2-02.2.2.A3