Permit Number: T02CM02602
Parcel: 132191160

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T02CM02602
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/24/2002 MIKE BERGHUIS FLOODPLAIN REVIEW Approved
05/30/2002 PATRICIA GEHLEN ZONING REVIEW Approved
06/13/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Approved
06/13/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Approved
06/18/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied E1
1) Please add a note to provide a disconnect for all appliances in accordance with 99NEC 422 part C.
2) Receptacles "a" and "b" appear to be swapped in the SPECIAL OUTLET SCHEDULE .
E2
1) Place an emergency fixture adjacent to the exit doors on the outside of the building. See IBC 1003.2.11.2-4
E3
1) MUA/EX WIRING DIAGRAM:
a) The controller must be within sight of both the control disconnect (single pole switch) and the power disconnect (power disconnect for the MUA/Ex loads needs to be installed) 99NEC 430-102 and 74
b) The contactor must be motor circuit rated.99NEC 110-3
c) Circuit B-12 (control power) should be depicted on the diagram.
2) Provide a disconnect (toggle switch) within sight of EF2 motor starter. 99NEC 430-74
E4
1) It appears both circuits A-17 and A-24 are loads that are in panel B circuits 10 and 12. As such it appears they should be removed from panel A.
GENERAL COMMENTS.
1) Provide IECC lighting budget calculations. A maximum of 1.7 watts per square foot is allowed.
2) Please return the plans I have already reviewed along with your next submission.
06/19/2002 JIM EGAN FIRE REVIEW Approved
07/12/2002 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied
07/16/2002 GERRY KOZIOL WWM REVIEW Approved
07/17/2002 TOM CLARK WATER REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/19/2002 LISA LESNY OUT TO CUSTOMER Completed