Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T02CM02602
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/24/2002 | MIKE BERGHUIS | FLOODPLAIN | REVIEW | Approved | |
| 05/30/2002 | PATRICIA GEHLEN | ZONING | REVIEW | Approved | |
| 06/13/2002 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 06/13/2002 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 06/18/2002 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | E1 1) Please add a note to provide a disconnect for all appliances in accordance with 99NEC 422 part C. 2) Receptacles "a" and "b" appear to be swapped in the SPECIAL OUTLET SCHEDULE . E2 1) Place an emergency fixture adjacent to the exit doors on the outside of the building. See IBC 1003.2.11.2-4 E3 1) MUA/EX WIRING DIAGRAM: a) The controller must be within sight of both the control disconnect (single pole switch) and the power disconnect (power disconnect for the MUA/Ex loads needs to be installed) 99NEC 430-102 and 74 b) The contactor must be motor circuit rated.99NEC 110-3 c) Circuit B-12 (control power) should be depicted on the diagram. 2) Provide a disconnect (toggle switch) within sight of EF2 motor starter. 99NEC 430-74 E4 1) It appears both circuits A-17 and A-24 are loads that are in panel B circuits 10 and 12. As such it appears they should be removed from panel A. GENERAL COMMENTS. 1) Provide IECC lighting budget calculations. A maximum of 1.7 watts per square foot is allowed. 2) Please return the plans I have already reviewed along with your next submission. |
| 06/19/2002 | JIM EGAN | FIRE | REVIEW | Approved | |
| 07/12/2002 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied | |
| 07/16/2002 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 07/17/2002 | TOM CLARK | WATER | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/19/2002 | LISA LESNY | OUT TO CUSTOMER | Completed |