Permit Review Detail
Review Status: Stopped
Review Details: SITE
Permit Number - T02CM02474
Review Name: SITE
Review Status: Stopped
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/17/2002 | MICHAEL ST. PAUL | ZONING | REVIEW | Passed | |
| 05/17/2002 | MICHAEL ST. PAUL | NPPO | REVIEW | Passed | |
| 05/17/2002 | MICHAEL ST. PAUL | LANDSCAPE | REVIEW | Passed | |
| 05/24/2002 | BLANCA ESPINO | FLOODPLAIN | REVIEW | Approved | |
| 05/24/2002 | BLANCA ESPINO | ENGINEERING | REVIEW | Denied | Site Plan 1. Will additional structure be made of the same material and style as the cultural ramada? Are these existing or proposed structures? 2. Indicate existing and future sight visibility triangles. D.S. 2-02.2.1.10 3. Indicate if streets are Private or Public. D.S. 2-02.2.1.18 4. Dimension right-of-way. D.S. 2-02.2.1.19 5. Indicate refuse container location, size and access thereto fully dimensioned. D.S. 2-02.2.1.32 |
| 05/24/2002 | BLANCA ESPINO | SANITATION | REVIEW | Denied | SEE ENGINEERING FOLDER |
| 05/29/2002 | PHIL SEADER | HANDICAP-SITE | REVIEW | Approved | |
| 06/04/2002 | JIM EGAN | FIRE | REVIEW | Denied |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/01/2002 | ELAINE ROSE | OUT TO CUSTOMER | Stop |