Permit Number: T02CM02446
Parcel: 11709035C

Address:
1005 S 7TH AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T02CM02446
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/13/2002 MATT FLICK FLOODPLAIN REVIEW Approved Floodplain: Previously reviewed and approved by Doug Williams on June 10 for site plan purposes.
08/15/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied See comments made on May 31,2002.
08/15/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied See comments made on May 31,2002.
08/30/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Approved
09/12/2002 JIM EGAN FIRE REVIEW Approved
09/19/2002 DAVE MANN BUILDING-COMMERCIAL REVIEW Denied This is a commercial project and all drawings should be prepared under the direction of an appropriate licensed professional and sealed and signed by them.

SH D2 Site Plan
· Remove ramp from access aisle. (See Sec. 502.4, ICC/ANSI A117.1-1998) Detail access to concrete walk from disabled access aisle.
· All units shall be accessible to the disabled.

SH A1 Floor Plan
· All dwelling units shall be Type B accessible units in accord w/ Sec. 1107.5.4, IBC 2000, revise accordingly, (See Section 1003, ICC/ANSI A117.1 - 1998)
· Provide professional seal and signatures for all disciplines.

SH S1 continued
· Provide head, jamb, and sill details with windows.

SH S2 COLLAR BEAM CONNECTION
· Verify design based upon size of window opening
SECTION B
· At primary entrances, dimension from top of threshold to finish floor and exterior landing as ½".
09/20/2002 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
8/29/02
Building plans may not be reviewed until the site/landscape/NPPO plans have been approved and are included in the submittal package

Final Status

Task End Date Reviewer's Name Type of Review Description
10/04/2002 ELAINE ROSE OUT TO CUSTOMER Completed