Permit Number: T02CM02446
Parcel: 11709035C

Address:
1005 S 7TH AV

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T02CM02446
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/17/2002 JIM EGAN FIRE REVIEW Denied
05/31/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plans need to sealed by a registered architect. 1. Provide the up stream M.H. Rim elev., Inverts on the civil plan. Provide the slope of the 6" sewer on the plan. 2. Provide a water demand calculation based on Appendix 'A' UPC1994 Az. Code. 3. Provide the manufactures name and listing for all of the plumbing fixtures. 4. Provide a complete waste line isometric drawing.
05/31/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical Plans need to sealed by a registered architect. 1. Model energy code calculations are not with plan set. 2. Mechanical design not with plan set.
06/14/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied
06/26/2002 PHIL SEADER BUILDING-COMMERCIAL REVIEW Denied
06/27/2002 MARK TITUS WATER REVIEW Approved
06/28/2002 LLESNY1 FLOODPLAIN REVIEW Needs Review
06/28/2002 LLESNY1 ZONING REVIEW Needs Review
06/28/2002 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/25/2002 CINDY AGUILAR OUT TO CUSTOMER Completed