Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T02CM02446
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/17/2002 | JIM EGAN | FIRE | REVIEW | Denied | |
| 05/31/2002 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | Plans need to sealed by a registered architect. 1. Provide the up stream M.H. Rim elev., Inverts on the civil plan. Provide the slope of the 6" sewer on the plan. 2. Provide a water demand calculation based on Appendix 'A' UPC1994 Az. Code. 3. Provide the manufactures name and listing for all of the plumbing fixtures. 4. Provide a complete waste line isometric drawing. |
| 05/31/2002 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | Mechanical Plans need to sealed by a registered architect. 1. Model energy code calculations are not with plan set. 2. Mechanical design not with plan set. |
| 06/14/2002 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | |
| 06/26/2002 | PHIL SEADER | BUILDING-COMMERCIAL | REVIEW | Denied | |
| 06/27/2002 | MARK TITUS | WATER | REVIEW | Approved | |
| 06/28/2002 | LLESNY1 | FLOODPLAIN | REVIEW | Needs Review | |
| 06/28/2002 | LLESNY1 | ZONING | REVIEW | Needs Review | |
| 06/28/2002 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/25/2002 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |