Permit Number: T02CM02425
Parcel: 115154820

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM

Permit Number - T02CM02425
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/14/2002 DAN CASTRO ZONING REVIEW Approved
05/14/2002 DAN CASTRO NPPO REVIEW Passed
05/14/2002 BLANCA ESPINO FLOODPLAIN REVIEW Approved
05/24/2002 TERRY STEVENS BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM0T02CM02425

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

FOUNDATION PLANS:

1. NOTE AND DETAIL MINIMUM REINFORCING, OR PROVIDE CODE JUSTIFICATION OF ALTERNATE:
- STEMWALL - ONE (1) #4 REBAR IN THE BOTTOM OF THE FOOTING AND ONE (1) #4 REBAR IN THE TOP OF THE
STEM ON BRACED WALLS PER R602.10.6

STRUCTURAL PLANS:

1. SPECIFY DESIGN CRITERIA ON PLANS. VALUES FOR FLOOR DEAD LOAD AND LIVE LOAD, ROOF DEAD LOAD
AND LIVE LOAD.

2. DETAIL ALL CONNECTIONS AND CROSS-REFERENCE TO THE FOUNDATION AND FRAMING
PLANS:
- DETAIL SHOWS TRUSSES TO TOP PLATE-ROOF PLAN CALL FOR 2X10- RAFTERS
- BEAM TO COLUMN
- CLOUMN TO FOOTER
- CONTINUOUS LOAD PATH FOR SHEAR TRANSFER

3. SUBMIT STRUCTURAL CLAC'S ON 2X 10 RAFTER CANiTLEVER- 7'

4. NOTE AND SPECIFY THE ANCHORING BEAMS TO MASN COLUMNS


PLUMBING PLANS:

1. PROVIDE PRESSURE AND TEMPERATURE RELIEF VALVE AT WATER HEATER.

2. NOTE: AS OF 2-02-01 THE CITY OF TUCSON HAS ADOPTED THE 2000 IRC EXCEPT FOR THE PLUMBING PORTION WHICH IS THE STATE PLUMBING CODE. ALL MODEL PLANS SHALL BE REFERENCE TO THE PREVIOUSLY MENTIONED CODES.

MECHANICAL PLANS:

1. GAS APPLIANCES SHALL COMPLY WITH CHAPTER 17 COMBUSTION AIR REQUIREMENTS. DETAIL HOW. MIN. 110 SQ. INCHES REQUIRED

IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
REYES ARVAYO @ 791-5550 EXT. 113
05/29/2002 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/03/2002 MONICA VALDEZ OUT TO CUSTOMER Completed