Permit Number: T02CM02412
Parcel: 109250550

Review Status: Completed

Review Details: 3RD PARTY REVIEW-REVISION/OTHER

Permit Number - T02CM02412
Review Name: 3RD PARTY REVIEW-REVISION/OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/30/2003 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied GENERAL:

q The reference set submitted is incomplete. The only plumbing sheet included in the reference set was Sheet P2 which contains schedules. Where is the most current approved Sheet P1 which contains the plumbing floor plan? Please provide.

ARCHITECTURAL:

q There are no architectural comments to be addressed.

STRUCTURAL:

q There are no structural comments to be addressed.

MECHANICAL:

q There are no mechanical comments to be addressed.

PLUMBING:

q Are the changes to be reviewed the red lines marked on the two copies of Sheet ASP which have been submitted? What do these red lines represent (water, sewer, gas)? Are the red lined boxes water or gas meters? Has the professional registrant (the civil or the mechanical engineer) reviewed this change to his plans? Please clarify.

ELECTRICAL:

q There are no electrical comments to be addressed.

-End of Review-

Final Status

Task End Date Reviewer's Name Type of Review Description
05/30/2003 ELAINE ROSE OUT TO CUSTOMER Completed