Permit Number: T02CM02305
Parcel: 11006152B

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM

Permit Number - T02CM02305
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/07/2002 PETER MCLAUGHLIN ZONING REVIEW Approved
05/07/2002 PETER MCLAUGHLIN NPPO REVIEW Passed
05/07/2002 JAMES TATE FLOODPLAIN REVIEW Approved
05/20/2002 TERRY STEVENS BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM02305

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

GENERAL REQUIREMENTS:

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

SITE PLAN:

1. INDICATE THE LOCATION OF ELECTRIC LINE FOR NEW DUAL PACK AND LOCATIONS OF GAS METERS ON THE PROPERTY, AND WHERE THEY ENTER THE BUILDING.

FOUNDATION PLANS:

1. NOTE ON THE DRAWINGS THE ALLOWABLE SOIL BEARING PRESSURE USED IN THE DESIGN OF THE FOOTINGS,
OR STATE THAT THE ASSUMED VALUE OF 1500 PSF IS BEING USED, PER TABLE R401.4.1, A SOILS REPORT IS
NOT REQUIRED. IT IS UP TO THE DESIGNER/HOMEBUILDER TO BE AWARE OF THE SOIL AND CONDITIONS OF
THE SITE. IF SOIL TESTING HAS BEEN DONE, A COPY OF THE SOILS REPORT SHALL BE SUBMITTED WITH THE
CONSTRUCTION PLANS, AND THE FOUNDATION DESIGN SHALL REFLECT THE SOILS REPORTS
RECOMMENDATIONS.

2. DIMENSION THE FOOTING WIDTH [MIN. 16"] AND DEPTH INTO UNDISTURBED SOIL [ MIN. 12"] FOR EACH FOOTING TYPE AND CONDITION PER TABLE R403.1.

3. FOOTING WIDTHS FOR ONE-STORY, PER TABLE R403.1:
- 16" MINIMUM; WOOD FRAME

4. ALL SLABS AND PADS, INCLUDING LANDINGS AT ALL DOORS, SHALL BE SHOWN AND THEIR THICKNESS
SPECIFIED. INDICATE THE SLOPE FOR EXTERIOR SLABS, PER R312.

FLOOR PLANS:

1. PROVIDE ALL WINDOW SIZES AND TYPES, AND DESIGNATE THE OPERABLE PORTION OF WINDOWS, AS WELL
AS THE LOCATIONS OF TEMPERED GLASS PER R308.4.

2. SHOW COMPLIANCE WITH R310 PROVIDING EGRESS FROM BEDROOMS.
- MAXIMUM SILL HEIGHT OF 44"
- MINIMUM NET CLEAR AREA OF OPENING OF 5.7SF.
- MINIMUM NET CLEAR DIMENSIONS OF OPENING OF 24" HEIGHT BY 20" WIDTH.

3. PROVIDE ACCESS TO EACH SEPARATE ATTIC AND CRAWL SPACE THAT EXCEEDS 30SF. DESIGNATE
LOCATIONS ON THE DRAWINGS. OPENINGS SHALL NOT BE LESS THAN 22" BY 30". THE ATTIC ACCESS SHALL
PROVIDE A MINIMUM OF 30" OF HEADROOM, AND SHALL BE LOCATED IN A HALLWAY OR READILY
ACCESSIBLE SPACE PER R807.

4. A ONE HOUR RATED FIREWALL IS REQUIRED BETWEEN THE TWO UNITS. PROVIDE DETAIL [CROSS SECTION] OF HOW THE WALL WILL BE BUILT. NOTE: THE WALL MUST EXTEND FROM THE FLOOR TO THE BOTTOM OF THE ROOF DECK.

5. NOTE THAT BATHTUB AND SHOWER ENCLOSURES SHALL BE FINISHED PER p2710 WITH CERAMIC TILE, OR A
LISTED ENCLOSURE, TO A HEIGHT OF 72" ABOVE THE DRAIN PER R702.4 AND R307.2

6. IDENTIFY CEILING HEIGHTS IN ALL AREAS ON FLOOR PLAN. IF SLOPED CEILING, NOTE AVERAGE HEIGHT.

STRUCTURAL PLANS:

1. SPECIFY DESIGN CRITERIA ON PLANS. VALUES FOR FLOOR DEAD LOAD AND LIVE LOAD, ROOF DEAD LOAD
AND LIVE LOAD.

2. PROVIDE COMPLETE ROOF FRAMING PLANS. CROSS REFERENCE ALL CONNECTION DETAILS, HEADER TYPES, ETC. TO KC PANEL BOOK OR PROVIDE DETAILS ON THE PLANS WITH CROSS REFERENCES.

3. PROVIDE MANUFACTURER'S CALCULATIONS AND DATA FOR PRE-FAB TRUSSES AND GLULAM BEAMS. TRUSS
CALCULATIONS MUST BE SIGNED, DATED AND WET-SEALED BY AN ENGINEER WHO IS REGISTERED IN
ARIZONA. TRUSS CALCULATIONS SHALL BE CROSS-REFERENCED TO THE FLOOR PLANS.
NOTE: TRUSS CALCS. PROVIDED INDICATE A 51/2" BEARING SURFACE. PLANS INDICATE A 41/2"TOP PLATE. CHANGE TRUSS CALCS. OR WALL THICKNESS.

4. DETAIL GABLE END BRACING CONNECTIONS.

5. COMPLETELY DETAIL ALL CONNECTIONS AND CROSS-REFERENCE TO THE FOUNDATION AND FRAMING
PLANS:

6. DETAIL ALL SHEAR CONNECTIONS FROM THE FOUNDATION TO THE ROOF PLYWOOD.

ELEVATIONS:

1. SHOW CALCULATION OF ATTIC VENTILATION AREA IN COMPLIANCE WITH R806.2. NOTE LOCATION OF ALL
VENTS NEEDED TO COMPLY.

SECTIONS - DETAILS - MISC. NOTES:

1. CROSS-SECTIONS SHALL BE CROSS-REFERENCED TO THE FLOOR PLAN AND FRAMING PLANS.

PLUMBING PLANS:

1. NOTE AND SPECIFY ALL PIPING MATERIALS.
NOTE: PVC CANNOT BE USED INSIDE OF THE BUILDING

2. GAS: PROVIDE THE LENGTH OF LINE TO EACH APPLIANCE, BTU DEMAND OF EACH APPLIANCE, SIZE OF
EACH BRANCH, TOTAL DEMAND & TOTAL DEVELOPED LENGTH FROM METER TO MOST REMOTE
APPLIANCE ON THE SYSTEM PER UPC 1217.2
NOTE: MECH. PLAN INDICATES A 90000 BTU GAS PACK, PLUMBING PLAN INDICATES A 65000 BTU ROOF TOP FURNACE, AND ELEC. PLAN INDICATES HEATPUMP---CLARIFY.

3. WATER LINE: PROVIDE TOTAL FIXTURE DEMAND & MAXIMUM DEVELOPED LENGTH

4. NOTE ON PLAN COMPLIANCE WITH WATER CONSERVATION; WATER CLOSETS 1.6 GALLONS PER FLUSH, SINKS
AND SHOWERHEADS 3 GALLONS PER MINUTE.

5. PROVIDE PRESSURE AND TEMPERATURE RELIEF VALVE AT WATER HEATER.
NOT TO WASHER DRAIN BUT TO OUTSIDE SOURCE

6. NOTE ON PLANS THAT SHOWER AND TUB / SHOWER COMBINATIONS THAT HAVE INDIVIDUAL CONTROL
VALVES SHALL BE OF THE PRESSURE BALANCE OR THERMOSTATIC MIXING VALVE TYPE.

7. THE CITY OF TUCSON HAS NOT ADOPTED THE PLUMBING SECTION OF THE IRC 2OOO. THE CURRENT CODE BEING USED IS THE 1994 UPC WITH THE STATE AMENDMENTS. ALL PLANS MUST REFERENCE TO THIS CODE.

MECHANICAL PLANS:

1. NOTE ON PLANS: MECHANICAL SHALL COMPLY WITH CHAPTERS 12 -16 AND18- 24 2000 IRC.

2. THE DWELLING MUST BE PROVIDED WITH HEATING CAPABLE OF MAINTAINING A ROOM TEMPERATURE OF
68 DEGREES AT A POINT 3' ABOVE THE FLOOR PER R303.6.
NOTE: IS GAS PACK/FURNACE/HEATPUMP ROOF MOUNTED OR ATTIC MOUNTED-----CLARIFY

3. IF THE HEATING OR AIR CONDITIONING EQUIPMENT IS LOCATED IN THE ATTIC, SHOW LOCATION OF ACCESS,
CATWALK AND WORKING PLATFORM. SHOW PROVISIONS FOR AND ROUTE OF SECONDARY CONDENSATE
DRAIN PER M1305.1.3.

ELECTRICAL PLANS:

1. NOTE ON PLANS: ELECTRICAL WORK SHALL COMPLY WITH CHAPTERS 33 - 42, 2000 IRC.

2. DESIGNATE THE LOCATION AND CIRCUIT OF ALL REQUIRED LIGHT FIXTURES, RECEPTACLE OUTLETS, POWER
OUTLETS AND SWITCHES. PROVIDE A PANEL SCHEDULE NOTING CIRCUIT NUMBER AND SIZE ALONG WITH A
GENERAL DESCRIPTION.
NOTE: 60 AMP BREAKERS REQUIRE #6 WIRE
20 AMP BREAKERS REQUIRE #12 WIRE
30 AMP BREAKER WITH #2 WIRE?
PANEL INDICATES A 200 AMP PANEL ON A 125 AMP SERVICE--------CLARIFY
SEVERAL RECEPTS NOT CROSS REFERENCED TO PANEL

3. RECEPTACLE OUTLETS SHALL BE PROVIDED AT EACH KITCHEN COUNTER SPACE WIDER THAN 12", AND
SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24" FROM A RECEPTACLE
OUTLET, PER E3801.4.1

4. NOTE THAT TWO OR MORE 2OAMP SMALL APPLIANCE CIRCUITS SHALL BE PROVIDED TO SERVE ALL
RECEPTACLE OUTLETS IN THE KITCHEN, BREAKFAST ROOM AND DINING ROOM. SUCH CIRCUITS SHALL
HAVE NO OTHER OUTLETS, PER E3603.2 AND E3801.3-4.5.

5. NOTE THAT AT LEAST ONE 20-AMP BRANCH CIRCUIT SHALL BE INSTALLED TO SERVE THE LAUNDRY ROOM,
AND THIS CIRCUIT SHALL HAVE NO OTHER OUTLETS, PER E33603.3 AND 3801.8.

6. INDICATE THE LOCATION OF ALL AIR CONDITIONING AND HEATING UNITS, AIR HANDLERS, COMPRESSORS
AND DISCONNECTS.

7. INDICATE THE LOCATION OF CONVENIENCE OUTLET AND LIGHT SWITCH FOR ATTIC HEATING AND AIR
CONDITIONING EQUIPMENT PER E3801.11 AND E3803.4.---IF APPLYS

8. WHERE CEILING FANS ARE SHOWN ON THE PLANS, PROVIDE A NOTE INDICATING ONLY APPROVED
OUTLET BOXES SHALL BE USED, PER E4001.6.

MODEL ENERGY CODE:

1. PROVIDE TWO COPIES OF ENERGY CALCULATIONS PER THE 1998 IECC, OR COMPLY WITH IRC CHAPTER 11.

2. CALL OUT ON THE PLANS THE "R" VALUES OF INSULATION, AS WELL AS THE "U" VALUES OF THE WINDOWS
AND DOORS IN CONFORMANCE WITH THE ENERGY CALCULATIONS PROVIDED.

IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
TERRY STEVENS @ 791-5550 EXT. 112
05/21/2002 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/30/2002 LISA LESNY OUT TO CUSTOMER Completed