Permit Number: T02CM02284
Parcel: 13101002H

Address:
5000 E 29TH ST

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T02CM02284
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/07/2002 JIM EGAN FIRE REVIEW Approv-Cond
05/07/2002 RONALD ENGELKES WATER REVIEW Approved
05/16/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical 1. A smoke detector shall be installed in the return air duct of AC-1 Per Sec606.2.1IMC2000. 2. Show on the plan how the kitchen exaust complies with Sec508.1IMC2000.
05/16/2002 PATRICIA GEHLEN ZONING REVIEW Approved
05/16/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing 1. Why would a backwater valve be required under the 1994UPC Az. Code? 2. Gas line can not be installed under slab and roof Sec1211.3UPC1994Az.Code. 3. Could find only 2ea P-6 lav's on the plan.
05/21/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied GENERAL COMMENTS
1) See the red line set in addition to my written comments for further clarification.
2) Provide IECC Light budget calculations.
3) Please return the redline set along with your next submission. This will assist in my second review.
E0.1
1) Provide fixture cuts and catalog numbers for luminaires K, U, Q.
E2.1
1) HS 32 serving TU2 and TU3 should be HS-30.
2) A receptacle with a circuit number 14 is connected to LS-12, 22.
3) Provide a minimum 60 amp disconnect for AC-1. 99NEC 440-12(b)(2).
4) Circuit LS-26 serving EF1 and EF4 should be circuited to LS-30.
5) A receptacle with a #16 adjacent to it should connect to circuit LN-29
6) A receptacle with a #16 adjacent to it should connect of circuit LN-18.
7a) CU-1 requires a 208/1 phase connection with a load of 9.6 amps (1997 VA).
7b) This requires circuiting CU-1 to LS 31,33, and the door operator to circuit LS 35 on the plan and in the panel schedule.
E2.2
1) Provide dual switching everywhere except areas with only 1 luminaire, occupancy sensors, corridors, storage rooms, restrooms, and public lobbies. See 98IECC 705.2.1
2) 2000IBC 1003.2.11.2 (4) requires emergency lighting on the exterior exit discharge immediately adjacent to the exit discharge.
E8.1
1a) Panel LS has a 175 amp MCB on page E8.1 and a 225 amp MCB on E8.2.
1b) Panel HS has a 70 amp circuit breaker for the transformer on page E8.1 and a 100 amp circuit breaker on page E8.2.
3) Circuit HS 37,39,41 describes a 45 kVA transformer on page E8.2 the one line describes it as a 75kVA.
4) Provide a 30 amp circuit breaker and #10 wire for HS 14,16,18. 99NEC 424-3(b)
E8.2
1) The main service has a fault at its line terminals of 42,246 amps however it is only braced for 32,600 amps.
2) Identify the A/Cs as AC#1 and AC#2.
06/25/2002 PHIL SEADER BUILDING-COMMERCIAL REVIEW Denied
06/26/2002 GERRY KOZIOL WWM REVIEW Approved
06/26/2002 MIKE BERGHUIS FLOODPLAIN REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/12/2002 CINDY AGUILAR OUT TO CUSTOMER Completed