Permit Number: T02CM02244
Parcel: 12912104B

Review Status: Completed

Review Details: REVISION

Permit Number - T02CM02244
Review Name: REVISION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/13/2003 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied .. T02CM02244 .. 1067 E SILVERLAKE RD .. DGL ..1/13/03.. .. 1. PROVIDE ADEQUATE GRADE ELEVATIONS TO SHOW CONFORMANCE WITH IBC CHAPTER 11 AND 34 AND ANSI A117.1-1998 FOR SIDEWALKS AND PARKING, INCLUDING ACCESS AISLE. ................................................................ .. 2. PROVIDE 'CLEAN' DRAWINGS FOR REVISIONS ,WITH NO EXISTING APPROVALS ON THEM WHEN RESUBMITTED DWGS G1.1,A4.0. .................................... .. 3. CLARIFY USE OF 'CODAC' AS OFFICE WITH OCCUPANT LOAD OF 7 vs MECHANICAL AND ELECTRICAL PLANS SHOWING ASSEMBLY STYLE SEATING FOR 21+ AS THIS WOULD REQUIRE A SECOND ACCESSIBLE TOILET ROOM, PER IBC CHAPTER 29, DWGS M1.1, E3.0.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/21/2003 MICHAEL ST. PAUL OUT TO CUSTOMER Completed