Permit Number: T02CM02243
Parcel: 12912104B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T02CM02243
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/10/2002 JIM EGAN FIRE REVIEW Approved
05/22/2002 DAN CASTRO ZONING REVIEW Approved
05/29/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Approved
05/29/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied E2
1) Although not a code requirement usual practice is to provide GFCI protection for all receptacles in near proximity to a sink. Typical both units.
2) There is an 11 adjacent to the exterior light in unit B. I believe it should be circuit B-10. Typical for B unit.
3) HPCU #1 should circuit to panel A. Typical for unit A.
4) Provide a receptacle and a light in the attic for servicing the AH. See 99NEC 210-63 and 210-70(c). Typical both units.
5) Provide a circuit and load for the 3kW hot water units. Typical both units.
E4
1) Circuits B-2/4 and B-4/6 require #6 and 8 copper conductors respectively.
2) Circuit B-5 appears in the panel schedule however I could not locate it on the plan.
GENERAL COMMENTS
E2
1) Provide a pole base width for the parking lot fixture.
2) Keynote #13 calls for a 20' foot pole however on page E4.0 a 30' pole is specified. If a 30' pole is utilized structural calculations prepared and sealed must be submitted for review.
05/29/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Approved
06/05/2002 JAMES TATE FLOODPLAIN REVIEW Denied Approved Site Plan required prior to building plan approval.
06/17/2002 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied SEE COMMENTS ATTACHED TO APPLICATION.
06/21/2002 GERRY KOZIOL WWM REVIEW Approved
06/21/2002 TOM CLARK WATER REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/25/2002 TAMI ACHONG OUT TO CUSTOMER Completed