Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T02CM02218
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/29/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 01/31/2003 | PETER MCLAUGHLIN | ZONING | REVIEW | Denied | Site plan must be approved before bldg plan approval. See site review comments dated jan 31, 2003. |
| 02/10/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide information showing that the submitted MEC calculations conform to the International Energy Conservation Code (1998). 2. Provide detail showing that the appliance closets in the 2- and 3-bedroom units comply with Sections 602.1 and 602.2.1, IMC (2000). |
| 02/10/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show routing and termination of condensate drains. Reference Sections 307.2.1 and 307.2.2, IMC (2000). 2. Show inverts and slope of building sewer line on drawing C1.1. 3. Recalculate plumbing schedule (shown on P1.2 and P1.3) using the values shown on Tables 7-3 and A-2, UPC. 4. Confirm the manufacturer's data and the minimum static pressure for P-3 is correct. 5. Recalculate pressure loss calculations and resize pipe in accordance with Sections 610.5 and 610.6, UPC. 6. Show how routing of drainage piping in Units 2, 4, 6, 7, and 9 conforms to Section 706.3, UPC. 7. Show routing and termination of T&P relief piping. Reference Section 608.5, UPC. 8. Resize drainage piping to conform to Table 7-5, UPC. 9. Clarify the waste and vent riser diagram. Are the vents to be combined or run separately through the roof? 10. Provide detail of water heater piping showing conformance to Section 608.3, UPC. 11. Provide reduced pressure backflow preventer assembly for site water supply. |
| 02/25/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/04/2003 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/06/2003 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |