Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T02CM02207
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/01/2002 | JIM EGAN | FIRE | REVIEW | Approved | |
| 05/01/2002 | ANY | FLOODPLAIN | REVIEW | Approved | |
| 05/01/2002 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 05/01/2002 | FRANK KALINSKI | WATER | REVIEW | Approved | |
| 05/23/2002 | WILDAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/08/2002 | WILDAN | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 07/08/2002 | WILDAN | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/08/2002 | WILDAN | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 07/09/2002 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/16/2002 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |